TLS RF Installation
Wiring the TLS RF
Figure 12 locates the diagnostic lights and setup switches in the TLS RF.
Each TLS RF in the site network must have a unique device set number (0,1,2 or 3). The factory default setting is
‘0’. You must select ‘0’ for the master TLS RF. The site’s Receiver must also be connected to the master TLS RF.
If a second TLS RF is required, enter ‘1’ in the auxiliary TLS RF. For additional TLS RFs, enter ‘2’ for the third and
‘3’ for the fourth.
Figure 12. TLS RF diagnostic LEDs and switch locations
LEGEND FOR NUMBERED BOXES IN Figure 12
1.
These LEDs flash when there is comm activity on RS-232 port
(Red = TX, Green = RX).
2.
These LEDs flash when there is comm activity on the RS-485
network (between TLS RF and Receiver).
3.
Red LED is lit when TLS RF is powered on.
4.
Device timeout rotary switch selects the maximum allowed
time to wait for communication from Transmitter before an
Comm alarm is posted by TLS console (see Appendix B for
selections). Position 1 (10 minutes) is the factory default set-
ting.
5.
These red LEDs flash when a message is received from a Trans-
mitter in the monitored device set. LED 1 is the device wired to
I.S. output terminal 1. LED 2 is the device wired to output termi-
nal 2, etc.
6.
Red LED flashes when TLS console is polling for device data.
7.
S2 DIP switches 1–2 enter device set address (see Appendix B).
964-12.ep
s
A
BCD
E
F
01
2
3
45
6
1
5
4
6
7
2
3
1
2
3
4
5
6
7
8
19-18