HydrX System Wiring
FCC & FC Power Wiring Connections To TLS-450Plus
26
Figure 27. Wiring Using an FE Petro DHI Box
Sump
Input
110V
Neutral
Disconnect, lock out,
and tag power at the
power panel before
wiring the pump.
WARNING
OFF
Maximum Exter
nal Contact
Closur
e Cir
cuit Ratings
12 Vdc, 0.015A
3
2
1
4
Maximum Relay Contact Ratings
120/240 V
ac, 5A 30 Vdc, 5A
Fuse Ratings 5A, 250 V
ac T
ype T (Slo-Blo)
2
1
5
3
4
Maximum AC
Input Ratings
120/240 V
ac, 0.10A
4
3
2
1
5
TN
2V
TN
2V
TN
2V
RTN
12V
I/O Module
FE STP - DHI
TLS-450PLUS
Output
110V
Fuse, 250 Vac, 1A
(fast acting type)
Neutral wire
terminal
Dispenser #1 (Supply &
Neutral), Typical wiring
for all dispensers
120V supply
wire terminal
Neutral
Unused
AT
G
AC Neutr
al
Inlet V
alve
N
Outlet V
alve
N
Pump Request
N
AC Line
Inlet V
alve
L
Outlet V
alve
L
Pump Request
L
11
10
9
8
7
6
5
4
3
2
1
FUEL CONDITIONING CONTROLLER (FCC) BOX
Junction Box
in Sump
120 Vac
L1 L2
Hook
Supply & Return
M1 M2
120 Vac
FC Outlet
Valve
NOTICE
• AC line on the FCC box, I/O module,
hook isolation box and dispenser inputs all need to
be on the same electrical phase.
• All conductors #14 THHN
• Switched neutral breaker required for source power
• Make ground connection in accordance with local codes.
If an E-stop is required by national or local codes or a local authority having jurisdiction, the HydrX
Fuel Conditioning Controller (FCC) power must be supplied by a 15 amp circuit that can be
interrupted by the same E-Stop as the FCC pump.
WARNING
FC Inlet
Valve
Pump Control Breaker
Neutral Bar
Ground Bar
15A Switched Neutral
SHUNTED FUEL PANEL
OR
LOAD SIDE OF E-STOP SYSTEM
PC2
PC3
PC4
PC4
SW2
FE STP - SCI OR VFC
1 2 3 4 5 6 7 8
ON
1 2 3 4 5 6 7 8
ON
SW1
+ G
RS-485
–
PC1
Pump control breaker
Neutral bar
G
ro
und bar
I/O module contact load
I/O module coil power
15A switched neutral L1
Inlet valve Hydrx
Outlet valve Hydrx
DHI dispenser input hot
15A switched neutral N
Inlet valve neutral
Outlet valve neutral
DHI dispenser input neutral
Unused
I/O module LV input RTN
I/O module LV input 12V
I/O module contact line side
I/O module coil neutral
Hydrx system ground
SCI/VFC hook terminal
DHI output
Hydrx controller #1
Hydrx controller #2
Hydrx controller #3
Hydrx controller #4
Hydrx controller #5
Hydrx controller #6
Hydrx controller #7
Hydrx controller #8
Hydrx controller #9
Hydrx controller #10
Hydrx controller #11
to
to
to
to
to
to
to
to
to
to
to
to
to
to
to
to
PC1
PC2
PC3
PC4
Содержание HydrX
Страница 1: ...Manual No 577014 446 Revision E HydrX FuelConditioning System Installation Manual...