Installation
Recommended Tools and Materials for Fuel Conditioner Installation
• Software Enhancement for HydrX Fuel Conditioning System (P/N 332972-032)
• Crescent wrench, large socket or custom tool – To remove 4” plug from manway plate
• Pipe wrench, chain wrench or strap wrench – To tighten the 4” stainless steel riser pipe w/flange
• Gas rated thread sealant – to put on the threads of the 4” stainless steel riser pipe.
• WID alignment tool – to align the WID Guide Tube before tightening it to the WID riser
• A 3/8” socket – to tighten the WID Guide Tube to the WID 4” riser/flange. Also to fasten the WID to the Guide
Tube
• A 11/16” and 7/8” open ended wrench, or adjustable wrench – to tighten the hose connections from the FCC
manifold to the WID, as well as the STP Adapter Assembly
• A 3-foot explosion proof flexible conduit, ½”electrical union, misc. ½” pipe nipples) - Miscellaneous electrical
fittings to connect the FCC junction box to the high power junction box in the STP sump.
• Tripod winch to lower Fuel Conditioner into sump - minimum safe load rating of 250 pounds.
WID Riser and Guide Tube Installation
1. Get the 4-inch stainless steel WID Riser with Guide Tube Flange from the kit. Apply a coating of fresh, UL
classified for petroleum, non-setting thread sealant on the threads of the riser and install it in the same 4”
manway fitting which was chosen in the HydrX Site Inspection Guide.
2. Figure
6 shows the preferred location for the WID Riser. Refer to your HydrX Site Inspection Guide to
determine the tank tilt. Since the Guide Tube directs the deployment of the Water Intake Device (WID), it must
be pointed in the direction of the pooling water. The Guide Tube orientation and WID configuration (1, 3, or 6
tubes) were determined by measurements made in your HydrX Site Inspection Guide.
3. Once the riser is installed, get the Guide Tube assembly and alignment bar from the kit. The Guide Tube is
inserted into the riser and sits on the riser flange. Example Guide Tube installations are shown in Figure
6 and
7.
Apply anti-seize compound to the threads of the four 1/4-20 WID flange bolts before
installing.