background image

Notice and Disclaimer

VEEDER-ROOT SHALL NOT BE LIABLE FOR ERRORS CONTAINED HEREIN OR FOR INCIDENTAL OR

 

CONSEQUENTIAL DAMAGES IN CONNECTION WITH THE FURNISHING, PERFORMANCE, OR USE

 

OF THIS PUBLICATION.

Please check for the latest version of this document online at 

www.veeder.com.

Veeder-Root makes no warranty of any kind with regard to this publication, including, but not limited to, the implied warranties of

 

merchantability and fitness for a particular purpose.

Veeder-Root shall not be liable for errors contained herein or for incidental or consequential damages

 

in connection with the furnishing, performance, or use of this publication.

Veeder-Root reserves the right to change system options or features, or the information contained in this publication.

This publication contains proprietary information which is protected by copyright. All rights reserved. No part of this publication

 

may be photocopied, reproduced, or translated to another language without the prior written consent of Veeder-Root.

Contact TLS Systems Technical Support for additional troubleshooting information at 800-323-1799.

DAMAGE CLAIMS / LOST EQUIPMENT

Thoroughly  examine all components and units  as  soon  as  they  are  received.  If any  cartons  are  damaged or  missing,  write  a

 

complete and detailed description of the damage or shortage on the face of the freight bill. The carrier's agent must verify the

 

inspection and sign the description. Refuse only the damaged product, not the entire shipment.
Veeder-Root must be notified of any damages and/or shortages within 30 days of receipt of the shipment, as stated in our Terms

 

and Conditions. 

VEEDER-ROOT’S PREFERRED CARRIER

1. Contact Veeder-Root Customer Service at 800-873-3313 with the specific part numbers and quantities that were missing

 

or received damaged.

2.  Fax signed Bill of Lading (BOL) to Veeder-Root Customer Service at 800-234-5350.

3. Veeder-Root will file  the claim with  the carrier and  replace  the damaged/missing  product at no charge  to the  customer.

 

Customer Service will work with production facility to have the replacement product shipped as soon as possible.

CUSTOMER’S PREFERRED CARRIER

1. It is the customer’s responsibility to file a claim with their carrier.

2. Customer may submit a replacement purchase order. Customer is responsible for all charges and freight associated with

 

replacement order. Customer Service will work with production facility to have the replacement product shipped as soon as

 

possible.

3. If “lost” equipment is delivered at a later date and is not needed, Veeder-Root will allow a Return to Stock without a restocking

 

fee.

4. Veeder-Root will NOT be responsible for any compensation when a customer chooses their own carrier. 

RETURN SHIPPING

For the parts return procedure, please follow the appropriate instructions in the "General Returned Goods Policy” pages in the

 

"Policies and Literature" section of the Veeder-Root 

North American Environmental Products

 price list. Veeder-Root will not

 

accept any return product without a Return Goods Authorization (RGA) number clearly printed on the outside of the package.

NOTE: 

Contact Veeder-Root Technical Support for warranty claim assistance at 800-873-3313.

 ©Veeder-Root 2021. All rights reserved

.

Содержание HydrX

Страница 1: ...Manual No 577014 446 Revision E HydrX FuelConditioning System Installation Manual...

Страница 2: ...of any damages and or shortages within 30 days of receipt of the shipment as stated in our Terms and Conditions VEEDER ROOT S PREFERRED CARRIER 1 Contact Veeder Root Customer Service at 800 873 3313...

Страница 3: ...d Guide Tube Installation 10 Water Intake Device Installation 13 Fuel Conditioner FC Installation 14 Attaching FC Valve Wiring Conduit 14 Installing FC Into Sump 15 STP Adapter Assembly Installation T...

Страница 4: ...17 Figure 17 FC Hose Connection Mock Up 18 Figure 18 FC Hose Connection Installed 18 Figure 19 FC Manifold Hose Connections 19 Figure 20 WID Hose Connections 20 Figure 21 FCC Dimensions 21 Figure 22...

Страница 5: ...ng USM interfaces to Veeder Root protocol digital devices as well as switched pump control via IOM relays see Figure 1 Figure 1 HydrX Components The HydrX system includes an in sump Fuel Conditioner F...

Страница 6: ...sembly The Fuel Conditioner FC Assembly connects to the STP and to the Water Intake Device WID at the top of the WID Riser The FC returns processed fuel to the tank through a port in the Guide Tube fl...

Страница 7: ...the FCC Figure 4 FCC Guide Tube Water Intake Device WID The WID Riser has a special flange which supports the Guide Tube and which allows the Guide Tube to be oriented towards the pooled water at the...

Страница 8: ...rnings in the manuals listed in this document above and any other Federal State or Local requirements Warranty Registrations may only be submitted by selected Distributors Related Manuals 577014 466 H...

Страница 9: ...minor or moderate injury WEAR EYE PROTECTION Wear eye protection when working with pressurized fuel lines to avoid possible eye injury NOTICE is used to address practices not related to physical injur...

Страница 10: ...ive to your safety and the safety of others to understand the procedures before beginning work Make sure your employees and any service contractors read and follow the instructions WARNING This produc...

Страница 11: ...service contractors need to understand and comply with this program completely to ensure safety while the equipment is down Before you start work know the location of the Emergency Power Cutoff Switch...

Страница 12: ...the environment such as Carol C2534 or Belden 88760 8760 8770 or similar Throughout this manual when mentioning any cable or wire being used for probe and sensor to console wiring it will be referring...

Страница 13: ...r monitoring well location Gasketing or sealing compound must be used at each entry to the junction box to ensure a waterproof junction The interior volume of each junction box must be a minimum of 16...

Страница 14: ...e STP sump Tripod winch to lower Fuel Conditioner into sump minimum safe load rating of 250 pounds WID Riser and Guide Tube Installation 1 Get the 4 inch stainless steel WID Riser with Guide Tube Flan...

Страница 15: ...Installation WID Riser and Guide Tube Installation 11 Figure 6 Guide Tube Installation Example Tank Tilting Away From Manway...

Страница 16: ...Installation WID Riser and Guide Tube Installation 12 Figure 7 Guide Tube Installation Example Tank Tilting Toward Short End of The Tank...

Страница 17: ...ile pushing the tube s metal rectangular end down into the Guide Tube flange see Figure 8 Continue uncoiling pushing the tubing assembly down until the WID flange seats against the Guide Tube flange S...

Страница 18: ...C inlet outlet valves be installed as shown in Figure 10 V R Conduit Kit P N 330020 885 contains all of the necessary parts shown in the figure Apply anti seize to the threads of the conduit component...

Страница 19: ...roximate 145 pound weight of the assembly Loosen the two supporting clamps on the FC if necessary so they are open enough to clear the WID Riser 3 Utilizing a tripod and winch connected to the FC eyeb...

Страница 20: ...ressure before proceeding with this installation 1 Get the STP Adapter Assembly from the kit 2 Remove one of the siphon port plugs from the STP see Figure 13 Figure 13 Locating TRJ Siphon Port Plugs 3...

Страница 21: ...proceeding with this installation 4 Get the STP Adapter Assembly from the kit see Figure 15 Figure 15 FE Petro STP Adapter Assembly 5 Remove the 3 8 NPT siphon port plug from the STP see Figure 13 Fi...

Страница 22: ...llation 18 Attaching Hoses Between HydrX System In Sump Components Figure 17 shows a FC manifold hose connection mock up and Figure 18 is an example installation Figure 17 FC Hose Connection Mock Up F...

Страница 23: ...e pump extractable close the STP Adapter Assembly valve and loosen this hose connection and drain the hose Once the hose has drained move it out of the way as you lift out the extractable The STP Adap...

Страница 24: ...to the fitting marked T on the front of the FC Manifold see Figure 19 Tighten the fittings at both ends of the hose 6 Place the flaretite seal from the kit onto the male 1 2 JIC elbow fitting labeled...

Страница 25: ...tion Get the FCC mounting bracket hardware from the kit Attach the four brackets from the kit to the four corners of the unit with the supplied screws see Figure 22 Mark the holes on the wall and moun...

Страница 26: ...THROUGH RIGID CONDUIT 1 Open the existing Intrinsically Safe I S sensor s junction box for the Fuel Conditioner I S wiring connections Insert the cables from the FC Mag Probe and FC Pressure Sensor in...

Страница 27: ...HydrX System Wiring Fuel Conditioner Intrinsically Safe Wiring Connections 23 Figure 24 Epoxy Sealing FC Mag Probe and FC Pressure Sensor Field Connections...

Страница 28: ...minutes of continuous use Off Disable On Enable 5 Slave turn off drop helper when demand decreases Off Disable On Enable 6 8 Not used 2 8 5 4 3 7 6 1 0 9 MAG VFC Controller SW1 SW2 SW3 SW6 1 2 3 4 5...

Страница 29: ...by national or local codes or a local authority having jurisdiction the HydrX Fuel Conditioning Controller FCC power must be supplied by a 15 amp circuit that can be interrupted by the same E Stop as...

Страница 30: ...THHN Switched neutral breaker required for source power Make ground connection in accordance with local codes If an E stop is required by national or local codes or a local authority having jurisdicti...

Страница 31: ...an E stop is required by national or local codes or a local authority having jurisdiction the HydrX Fuel Conditioning Controller FCC power must be supplied by a 15 amp circuit that can be interrupted...

Страница 32: ...present If not present before insatllation of Hydrx it does not need to be added All conductors 14 THHN Make ground connection in accordance with local codes Terminal Block neutral EN DIESEL DIESEL A...

Страница 33: ...local codes If an E stop is required by national or local codes or a local authority having jurisdiction the HydrX Fuel Conditioning Controller FCC power must be supplied by a 15 amp circuit that can...

Страница 34: ...al codes or a local authority having jurisdiction the HydrX Fuel Conditioning Controller FCC power must be supplied by a 15 amp circuit that can be interrupted by the same E Stop as the FCC pump WARNI...

Страница 35: ...round lug on the module the other end at the probe or sensor is NOT grounded 3 Write in the device name for each wire connection on the connector block in the module s wiring label attached to the ins...

Страница 36: ...essure Sensor Wiring to TLS 450PLUS 32 Figure 32 TLS 450PLUS Access 1 Refer to Figure 33 below for TLS 450PLUS FC Mag Probe and FC Pressure Sensor wiring connections Figure 33 FC Mag Probe Pressure Se...

Страница 37: ...33 FCC RS 232 Serial Communication Wiring To TLS 450Plus Figure 34 diagrams the RS 232 serial comm connection between the FCC and the TLS 450PLUS Figure 34 RS 232 Connections FCC to TLS 450PLUS...

Страница 38: ...ssure Sensor Replacement 330020 871 Kit TRJ STP Adapter Assembly Replacement 330020 870 Kit FE Petro Siphon Jet Access Port Adapter Assembly Replacement 330020 869 Kit Alignment Bar Optional1 330020 8...

Страница 39: ......

Отзывы: