TLC-FCR-2 Engineering Manual

 

 

Doc: 70-00-0081, Date: 20081219 

© 2008 Vector Controls Ltd. 

Page 1 

TLC-FCR-2  
Intelligent Fan Coil controller 

Features 

 

Low power energy consumption: < 1W per unit 

 

Relays switching for outputs each up to 300W 

 

Temperature control for 2 or 4-pipe fan coil systems.  

 

Large temperature range from –40°C to 70°C (-40°F to 158°F). 

 

Choose between one 3-point actuator and two binary 
heating/cooling stages 

 

Automatic fan control for three stage fans.  

 

Cost saving option with Economy functionality and set point 
limitations 

 

Control for single stage heating, cooling and fan only operation 
modes 

 

Password protected programmable user and control parameters 

o

 

Setpoint range limitation 

o

 

Access control for setpoints, fan speeds and mode 
change 

o

 

Access control for heat/cool change and time programs 

o

 

Select your display contents 

o

 

Selectable behavior after return from power failure 

 

Temperature display in Celsius or Fahrenheit 

Deluxe Version: 

 

Clock and time schedule functions 

 

Blue backlight for LCD 

 

Infrared remote controller option:  
With special features for Boost and delayed switching on or off  

Applications 

 

Air Only Systems:  

o

 

Constant Air Volume systems with three stage fans for single or dual duct systems 

 

Air/Water Systems:  

o

 

Fan Coil units for 2-pipe or 4-pipe systems  

o

 

radiator control, chilled ceiling 

 

Simple individual room control for hotel rooms, meeting rooms, etc.  

General Description 

The TLC-FCR-2 is a stand-alone electronic fan coil controller with one control loop. The TLC-FCR-2 features 1 NTC 
temperature sensor input and four binary outputs (Relays).  
A detailed parameterization is possible with the use of a simple configuration routine. The TLC-FCR-2 can be 
configured using the standard operation terminal. No special tools or software is required.  

Ordering 

Item Name 

Item code 

Variant 

Features 

TLC-FCR-2 
TLC-FCR-2-W01 

40-10 0017 

40-10 0017-01 

Standard 
Cooling only 

Fan coil controller with:  
1 TI int 
3 DO (Relay) Fan control 
2 DO (Relay) Binary valve control 

TLC-FCR-2-D 
TLC-FCR-2-D-W01 

40-10 0018 
40-10 0018-01 

Deluxe 
Cooling only 

Selection of valve actuators and fans 

Binary auxiliary devices: E.g. fans, on/off valves, etc.  Do not directly connect devices that exceed 2(1.2)A. Observe 
startup current on inductive loads! Do not connect more than one fan coil unit to one controller. 

Содержание TLC-FCR-2

Страница 1: ...al features for Boost and delayed switching on or off Applications Air Only Systems o Constant Air Volume systems with three stage fans for single or dual duct systems Air Water Systems o Fan Coil uni...

Страница 2: ...The unit consists of three parts 1 The mounting plate made of galvanized steel 2 The power case made of fire proof ABS plastic 3 The front part made of white fire proof ABS plastic Installation 1 Arra...

Страница 3: ...5 N L1 230V AC N DO1 DO2 DO3 Attention Switching power is limited to 230VAC 300W 6 DO4 RT CPU Plug Front part 7 DO5 Fan Low Fan Medium Fan High Heat OPEN Cool CLOSE Attention Switching power is limit...

Страница 4: ...ode it was in before the power failure The deluxe version includes a real time clock with a 48h backup battery powered through a super capacitor The time does not need to be re entered after a power f...

Страница 5: ...oriums that might be occupied during a certain time During this time the reset is not active The unit will not start itself when UNI mode is active It still needs to be manually activated This is to a...

Страница 6: ...ot pressing a button for more than 5 minutes Heat Cool Fan only change Pressing the OPTION button toggles Heating Cooling Fan only mode Access to Heat Cool change may be disabled with UP 03 Clock Setu...

Страница 7: ...g of fan speeds Repeatedly pressing the fan speed button steps through low medium high and automatic fan speeds Automatic fan speed will not be activated in FAN ONLY mode Boost Pressing the boost butt...

Страница 8: ...evel 9 Press the POWER button again so as to leave the menu The unit will return to normal operation if no button is pressed for more than 5 minutes User Parameters Parameter Description Setting Range...

Страница 9: ...nd cooling stages Step by step switching In order to reduce the startup load of large fan motors fan stages will be switched on and off step by step going through low and medium before activating high...

Страница 10: ...ting mode 40 60 C 160 F 24 C 76 F FC 02 Minimum setpoint limit in Cooling mode 40 60 C 160 F 18 C 65 F FC 03 Maximum setpoint limit in Cooling mode 40 60 C 160 F 30 C 87 F Controls configuration FC 04...