TLC-FCR-2 Engineering Manual

 

 

Doc: 70-00-0081, Date: 20081219 

© 2008 Vector Controls Ltd. 

Page 5 

Clock Operation and Time Schedules (Deluxe Version) 

TLC-FCR-2-D contains a real time clock. Up to 16 mode changes (not defined, Off, Economy, Comfort, University mode) 
based on weekdays and time may be programmed. See chapter operation on how to program switch times.  
The different scheduled mode changes have these effects: 

Name on display 

Function 

Override reset 

no 

Switching event not used 

 

OFF 

Operation mode changes to off mode 

Reset is active 

ECO 

Operation mode changes to economy mode 

Reset is not active 

ON 

Operation mode changes to comfort mode 

Reset is not active 

UNI 

Operation mode does not change  

Reset is not active 

 
UNI: University mode: This switching mode is used for rooms such as lecture rooms and auditoriums that might be 
occupied during a certain time. During this time the reset is not active. The unit will not start itself when UNI mode is 
active. It still needs to be manually activated. This is to avoid unnecessary heating or cooling of such rooms while they 
are not occupied.  
Override reset function: The override reset applies when the unit is manually switched on, while in scheduled off mode. 
The unit will switch automatically off when the reset time defined in UP13 expires. Setting UP13 to 0, disables the 
override reset.  
A blinking clock indicates that the time needs to be set. Time programs will not operate if the time is not defined. See 
chapter operation, advanced settings for instructions on how to set the time. 

Error messages 

The TLC-FCR-2 may display the following error condition:  
Err1: 

Temperature sensor faulty. The connection to the temperature sensor may be interrupted or the temperature 
sensor is damaged. The controller may only be used in manual mode.  

FP: 

Frost protection is active. 

 

Содержание TLC-FCR-2

Страница 1: ...al features for Boost and delayed switching on or off Applications Air Only Systems o Constant Air Volume systems with three stage fans for single or dual duct systems Air Water Systems o Fan Coil uni...

Страница 2: ...The unit consists of three parts 1 The mounting plate made of galvanized steel 2 The power case made of fire proof ABS plastic 3 The front part made of white fire proof ABS plastic Installation 1 Arra...

Страница 3: ...5 N L1 230V AC N DO1 DO2 DO3 Attention Switching power is limited to 230VAC 300W 6 DO4 RT CPU Plug Front part 7 DO5 Fan Low Fan Medium Fan High Heat OPEN Cool CLOSE Attention Switching power is limit...

Страница 4: ...ode it was in before the power failure The deluxe version includes a real time clock with a 48h backup battery powered through a super capacitor The time does not need to be re entered after a power f...

Страница 5: ...oriums that might be occupied during a certain time During this time the reset is not active The unit will not start itself when UNI mode is active It still needs to be manually activated This is to a...

Страница 6: ...ot pressing a button for more than 5 minutes Heat Cool Fan only change Pressing the OPTION button toggles Heating Cooling Fan only mode Access to Heat Cool change may be disabled with UP 03 Clock Setu...

Страница 7: ...g of fan speeds Repeatedly pressing the fan speed button steps through low medium high and automatic fan speeds Automatic fan speed will not be activated in FAN ONLY mode Boost Pressing the boost butt...

Страница 8: ...evel 9 Press the POWER button again so as to leave the menu The unit will return to normal operation if no button is pressed for more than 5 minutes User Parameters Parameter Description Setting Range...

Страница 9: ...nd cooling stages Step by step switching In order to reduce the startup load of large fan motors fan stages will be switched on and off step by step going through low and medium before activating high...

Страница 10: ...ting mode 40 60 C 160 F 24 C 76 F FC 02 Minimum setpoint limit in Cooling mode 40 60 C 160 F 18 C 65 F FC 03 Maximum setpoint limit in Cooling mode 40 60 C 160 F 30 C 87 F Controls configuration FC 04...

Отзывы: