TLC-FCR-2 Engineering Manual

 

 

Doc: 70-00-0081, Date: 20081219 

© 2008 Vector Controls Ltd. 

Page 4 

Display and Operation 

The operation terminal uses an LCD display and four operation buttons.  

 

Legend: 

1.

 

4-digit display of current value, time,  
control parameter or set point. 

2.

 

Unit of displayed value, °C, °F, % or none 

3.

 

Indication of fan speeds 

4.

 

4-digit display of current value, time, control 
parameter or set point. 

5.

 

Operation modes: 

Comfort mode, 

 Economy mode, , OFF Energy Hold Off  

6.

 

Symbols:  

Heating Active 

Cooling Active 

Schedule Set 

Fan Active 

Manual Override 

Frost Protection 

 

 

 

 

 

 

7.

 

Buttons for operating the controller 

POWER button: Pressing the button less than 2 sec toggles Economy and comfort modes. Pressing 
the button for more than 2 seconds switches the unit off.  

UP and DOWN buttons: change setpoints and parameters

  

OPTION button: used for changing fan speed and accessing advanced setup. Acts as Enter in 
parameter changing menu. 

8.

 

While the fan is in operation, the Fan symbol will be indicated and the active Fan speed is displayed in the 
vertical scale. Activation of heating or cooling coil is indicated by the blinking of the respective symbol in the 
lower left corner of the display. 

Power Failure 

All the parameters and set points are memorized and don’t need to be reentered. Depending on UP05 the unit will 
remain switched off, switch on automatically or return to the operation mode it was in before the power failure.  
The deluxe version includes a real time clock with a 48h backup battery powered through a super capacitor. The time 
does not need to be re-entered after a power failure.  

Frost Protection 

The controller will enter frost protection mode if the room temperature drops below 5°C (41°F). All heating outputs will 
be fully opened. Frost protection mode will be left once the temperature reaches 10°C  (50°F). Frost protection display 
will remain until a button is pressed. Frost protection can be enabled/disabled using user parameter UP-09 

Operation Modes 

 

Comfort: The unit is in full operation mode. All the control functions are operating according to their setpoints. 

The unit displays occupied mode.  

 

Economy: The set point is shifted according to parameters FC-04. The heating parameter is shifted down and 

cooling parameter up. The unit displays unoccupied mode. Fan speeds are limited to low fan speed. Economy 
operation may be disabled with UP-06.  

 

Energy Hold Off (EHO): The unit is switched off. All outputs are off. The temperature will still be monitored in 

order to activate the unit in case of frost. (If frost protection is enabled). Off and current time is displayed.  

Activation of operation modes 

 

Via operation terminal 

 

Clock: (Deluxe version only) Operation modes may automatically be switched according to daytime and 
weekday. The clock symbol will be indicated if time programs are activated.  

 

Infrared Remote Controller: (Deluxe version only) use OPR-1 to control the unit remotely 

Note: Time programs will not operate, if time is not set.  

2

 

3

 

4

 

7

 

1

 

6

 

5

 

Содержание TLC-FCR-2

Страница 1: ...al features for Boost and delayed switching on or off Applications Air Only Systems o Constant Air Volume systems with three stage fans for single or dual duct systems Air Water Systems o Fan Coil uni...

Страница 2: ...The unit consists of three parts 1 The mounting plate made of galvanized steel 2 The power case made of fire proof ABS plastic 3 The front part made of white fire proof ABS plastic Installation 1 Arra...

Страница 3: ...5 N L1 230V AC N DO1 DO2 DO3 Attention Switching power is limited to 230VAC 300W 6 DO4 RT CPU Plug Front part 7 DO5 Fan Low Fan Medium Fan High Heat OPEN Cool CLOSE Attention Switching power is limit...

Страница 4: ...ode it was in before the power failure The deluxe version includes a real time clock with a 48h backup battery powered through a super capacitor The time does not need to be re entered after a power f...

Страница 5: ...oriums that might be occupied during a certain time During this time the reset is not active The unit will not start itself when UNI mode is active It still needs to be manually activated This is to a...

Страница 6: ...ot pressing a button for more than 5 minutes Heat Cool Fan only change Pressing the OPTION button toggles Heating Cooling Fan only mode Access to Heat Cool change may be disabled with UP 03 Clock Setu...

Страница 7: ...g of fan speeds Repeatedly pressing the fan speed button steps through low medium high and automatic fan speeds Automatic fan speed will not be activated in FAN ONLY mode Boost Pressing the boost butt...

Страница 8: ...evel 9 Press the POWER button again so as to leave the menu The unit will return to normal operation if no button is pressed for more than 5 minutes User Parameters Parameter Description Setting Range...

Страница 9: ...nd cooling stages Step by step switching In order to reduce the startup load of large fan motors fan stages will be switched on and off step by step going through low and medium before activating high...

Страница 10: ...ting mode 40 60 C 160 F 24 C 76 F FC 02 Minimum setpoint limit in Cooling mode 40 60 C 160 F 18 C 65 F FC 03 Maximum setpoint limit in Cooling mode 40 60 C 160 F 30 C 87 F Controls configuration FC 04...

Отзывы: