TLC-FCR-2 Engineering Manual

 

 

Doc: 70-00-0081, Date: 20081219 

© 2008 Vector Controls Ltd. 

Page 10 

Configuration parameters for firmware version 2.2 

The TLC-FCR-2 can be adapted to wide variety of applications. The adaptation is done with parameters. The 
parameters can be changed on the unit without the need of additional equipment.  

Identifying the firmware version 

The parameters and functionality of controller depend on its firmware revision. It is therefore important to use a 
matching product version and parameter set. The firmware version is shown on the large LCD digits when pressing UP 
and DOWN buttons for more than 3 seconds simultaneously.  

Control Parameters (Access Code: 241) 

Warning! Only experts should change these settings! See user parameters for login procedure.  

Parameter Description 

Range 

Standard 

FC 00 

Minimum setpoint limit in Heating mode 

-40…60°C (160°F) 

16°C (61°F) 

FC 01 

Maximum setpoint limit in Heating mode 

-40…60°C (160°F) 

24°C (76°F) 

FC 02 

Minimum setpoint limit in Cooling mode 

-40…60°C (160°F) 

18°C (65°F) 

FC 03 

Maximum setpoint limit in Cooling mode 

-40…60°C (160°F) 

30°C (87°F) 

Controls configuration 

FC 04 

Economy temperature shift 

0…100°C (200°F) 

5.0°C (10°F) 

FC 05 

Switching Span Heating,  
Setting this value to 0 disables the auto fan speed function in 
heating mode 

0…100°C (200°F) 

1.5°C (3°F) 

FC 06 

Switching Span Cooling 
Setting this value to 0 disables the auto fan speed function in 
cooling mode 

0…100°C (200°F) 

1.0°C (2°F) 

FC 07 

Switching Hysteresis 

0…100°C (200°F) 

0.5°C (1°F) 

FC 08 

Mold Protection: OFF = Disabled, ON = Enabled 

ON, OFF 

OFF 

FC 09 

Delay OFF (Minimum running time) 

0…255s 

10s 

FC 10 

Delay ON (Minimum stopping time) 

0…255s 

10s 

FC 11 

2-pipe or 4-pipe system: OFF = 2-pipe, ON = 4-pipe system 

ON, OFF 

OFF 

FC 12 

Dead zone between heating & cooling set point X

DZ

 

0…100°C (200°F) 

1.0°C (2°F) 

FC 13 

Delay on Heat/Cool change over 

0…255 min 

5 min 

Output configuration 

FC 14 

Output setting, Binary or 3-point:  

OFF = Binary (DO4 Heating, DO5 Cooling) 
ON = 3-point output (DO4 OPEN, DO5 CLOSE) 

ON, OFF 

OFF 

FC 15 

Running Time in 3-point mode 

0…255 s 

90 s 

 

Содержание TLC-FCR-2

Страница 1: ...al features for Boost and delayed switching on or off Applications Air Only Systems o Constant Air Volume systems with three stage fans for single or dual duct systems Air Water Systems o Fan Coil uni...

Страница 2: ...The unit consists of three parts 1 The mounting plate made of galvanized steel 2 The power case made of fire proof ABS plastic 3 The front part made of white fire proof ABS plastic Installation 1 Arra...

Страница 3: ...5 N L1 230V AC N DO1 DO2 DO3 Attention Switching power is limited to 230VAC 300W 6 DO4 RT CPU Plug Front part 7 DO5 Fan Low Fan Medium Fan High Heat OPEN Cool CLOSE Attention Switching power is limit...

Страница 4: ...ode it was in before the power failure The deluxe version includes a real time clock with a 48h backup battery powered through a super capacitor The time does not need to be re entered after a power f...

Страница 5: ...oriums that might be occupied during a certain time During this time the reset is not active The unit will not start itself when UNI mode is active It still needs to be manually activated This is to a...

Страница 6: ...ot pressing a button for more than 5 minutes Heat Cool Fan only change Pressing the OPTION button toggles Heating Cooling Fan only mode Access to Heat Cool change may be disabled with UP 03 Clock Setu...

Страница 7: ...g of fan speeds Repeatedly pressing the fan speed button steps through low medium high and automatic fan speeds Automatic fan speed will not be activated in FAN ONLY mode Boost Pressing the boost butt...

Страница 8: ...evel 9 Press the POWER button again so as to leave the menu The unit will return to normal operation if no button is pressed for more than 5 minutes User Parameters Parameter Description Setting Range...

Страница 9: ...nd cooling stages Step by step switching In order to reduce the startup load of large fan motors fan stages will be switched on and off step by step going through low and medium before activating high...

Страница 10: ...ting mode 40 60 C 160 F 24 C 76 F FC 02 Minimum setpoint limit in Cooling mode 40 60 C 160 F 18 C 65 F FC 03 Maximum setpoint limit in Cooling mode 40 60 C 160 F 30 C 87 F Controls configuration FC 04...

Отзывы: