Humidistat TCY-BH
Doc: 70-00-0142, V1.4, 20160912
© Vector Controls GmbH, Switzerland
Page 8
Subject to alteration
www.vectorcontrols.com
Input configuration
CP 14
OFF = Temperature setback is disabled
ON = Temperature setback is enabled
ON, OFF
OFF
CP 15
Set point limit at full setback
0…100%
20%
CP 16
Lower temperature limit:
Outside temperature with maximum setback
The set point will be equal to the minimum set point limit
-40…60°C
-40…160°F
-30°C (-22°F)
CP 17
Upper temperature limit:
Outside temperature at begin of setback.
-40…60°C
40…160°F
0°C (32°F)
CP 18
Number of seconds taken into account to calculate the
averaging input signal.
Low value = fast response
High value = slow response
0…100
10
Temperature setback (TSET)
Shift the humidity set point towards a defined TSET set point CP15 depending on the outdoor temperature.
Temperature setback becomes active when the outside temperature drops below the activation limit of temperature
setback CP17. The full temperature setback is reached when the temperature reaches the full limit CP16. The actual
set point will in this case be equal to the TSET set point.
Temperature setback may be enabled with CP14.
Averaging function of input signal:
The averaging function is used to prevent unwanted fluctuation of sensor signals. The controller measures every
second the signal inputs. The input signal is built over a number of measured values. Select how many values should
be used to calculate the averaging signal. Control speed will slow down when a large number of samples are used for
an averaging signal. This should be taken into account when defining the control parameters.
Temperature setback
T [°C, F]
CP16
CP17
CP15
Setpoint
W