Humidistat TCY-BH

 

 

Doc: 70-00-0142, V1.4, 20160912 

© Vector Controls GmbH, Switzerland 

Page 8 

Subject to alteration 

www.vectorcontrols.com 

Input configuration 

CP 14 

OFF = Temperature setback is disabled 

ON = Temperature setback is enabled 

ON, OFF 

OFF 

CP 15 

Set point limit at full setback 

0…100% 

20% 

CP 16 

Lower temperature limit:  
Outside temperature with maximum setback 

The set point will be equal to the minimum set point limit 

-40…60°C 

-40…160°F 

-30°C (-22°F) 

CP 17 

Upper temperature limit:  

Outside temperature at begin of setback.  

-40…60°C 

40…160°F 

0°C  (32°F) 

CP 18 

Number of seconds taken into account to calculate the 

averaging input signal. 

Low value = fast response 
High value = slow response 

0…100 

10 

Temperature setback (TSET) 

Shift the humidity set point towards a defined TSET set point CP15 depending on the outdoor temperature.  
Temperature setback becomes active when the outside temperature drops below the activation limit of temperature 

setback CP17. The full temperature setback is reached when the temperature reaches the full limit CP16. The actual 

set point will in this case be equal to the TSET set point.  
Temperature setback may be enabled with CP14. 

 

Averaging function of input signal:  

The averaging function is used to prevent unwanted fluctuation of sensor signals. The controller measures every 

second the signal inputs. The input signal is built over a number of measured values. Select how many values should 

be used to calculate the averaging signal. Control speed will slow down when a large number of samples are used for 

an averaging signal. This should be taken into account when defining the control parameters.  

Temperature setback 

 

T [°C, F] 

CP16 

CP17 

CP15 

Setpoint 

Содержание TCY-BH

Страница 1: ...tion The TCY BH is a stand alone electronic binary humidity stat The TCY BH features one internal humidity sensor one external NTC temperature sensor input and two binary outputs Relays A detailed par...

Страница 2: ...witching type AC switching power DO1 DO2 Relays 2 1 2 A 250VAC max fan power 300W Environment Operation Climatic conditions Temperature Humidity To IEC 721 3 3 class 3 K5 0 C 50 C 32 F 122 F 95 R H no...

Страница 3: ...umidify CP11 ON FAN CP10 2 If CP11 ON FAN Dehumidify N L Power In DO1 Relay 2A NTC 10k 1 2 G0 G 24VAC DC 5 6 Q23 Q24 N L 3 4 Q13 Q14 N L DO2 7 8 B1 M RT ext NTC10k TCY BH Power In DO1 Relay 2A NTC 10k...

Страница 4: ...er capacitor The time does not need to be re entered after a power failure Error messages The TCY BH may display the following error condition Err1 Humidity sensor faulty The humidity sensor is damage...

Страница 5: ...time schedule Pro1 Pro4 by using UP DOWN keys and pressing the ENTER key 1 Enable or disable the Pro1 time schedule Choose ON or OFF with the UP DOWN keys The following steps will only be accessible...

Страница 6: ...key will show CODE 2 Select a password using UP or DOWN buttons Select 009 in order to get access to the user parameters 241 for controls parameters Press OPTION after selecting the correct password 3...

Страница 7: ...cles and thus the wear on associated equipment 0 100 3 CP 08 Delay OFF Minimum running time MM SS Prevents a too short running cycle for the control output by setting a minimum running time 00 00 to 9...

Страница 8: ...point towards a defined TSET set point CP15 depending on the outdoor temperature Temperature setback becomes active when the outside temperature drops below the activation limit of temperature setback...

Отзывы: