Humidistat TCY-BH

 

 

Doc: 70-00-0142, V1.4, 20160912 

© Vector Controls GmbH, Switzerland 

Page 7 

Subject to alteration 

www.vectorcontrols.com 

Control functions (code 241) 

Warning! Only experts should change these settings! See user parameters for login procedure.  

Parameter  Description 

Range 

Standard 

CP 00 

Minimum set point limit in humidification mode 

0…100% 

10% 

CP 01 

Maximum set point limit in humidification mode 

0…100% 

90% 

CP 02 

Minimum setpoint limit in de-humidification mode 

0…100% 

10% 

CP 03 

Maximum setpoint limit in de-humidification mode 

0…100% 

90% 

Controls configuration 

CP 04 

Economy humidity shift:  
The comfort (occupied) set point is shifted by the value set here. If 
humidifying is active the comfort set point will be decreased, if dehumidifying 
is active, the set point will be increased. (Enable with UP04.)  

0…100% 

10% 

CP 05 

This parameter is only used if CP10 = 0 

Dead zone span:  

The Dead Zone Span defines the deviation set point to input value required for 
the controller to switch from humidifying to dehumidifying or vice versa. The 

output is off while the measured value is within the dead zone span. A 
negative dead zone is not possible. 

0…100% 

10% 

CP 06 

This parameter is only used if CP10 = 0 
Delay on humidify – de-humidify change over 

0…255 min 

5 min 

CP 07 

Switching Hysteresis 
Defines the difference between switching on and switching off an output. A 
small hysteresis will increase the number of switching cycles and thus the wear 
on associated equipment. 

0…100% 

3% 

CP 08 

Delay OFF (Minimum running time) [MM:SS] 
Prevents a too short running cycle for the control output by setting a minimum 
running time

 

00:00 to 98:30

 

00:10s

 

CP 09 

Delay ON (Minimum stopping time) [MM:SS] 
Prevents a too short running cycle for the control output by setting a minimum 
stopping time 

00:00 to 98:30

 

00:10s

 

Output configuration 

CP 10 

Configuration of control mode 
0 = Both Humidification and de-humidification 
1 = W04 = Humidification only

 

2 = W05 = De-humidification only 

 

0 - 2 

TCY-BH:  

TCY-BH-W4:  

TCY-BH-W5: 

CP 11 

Enable fan (only if CP 10 ≠ 0) 

ON, OFF 

TCY-BH:  

OFF 

TCY-BH-W4:   ON 
TCY-BH-W5:  ON 

CP 12 

Start delay for fan [MM:SS] 

(Time the fan runs before control output starts) 

00:00 – 98:30

 

00:10

 

CP 13 

Stop delay for fan [MM:SS] 

(Time the fan keeps running after control output stops)

 

00:00 – 98:30

 

01:30

 

Control logic TCY-BH 

System type 

CP10 

CP11 

DO1 

DO2 

Humidify and de-humidify 

OFF 

Humidifying 

Dehumidifying 

Humidify only 

OFF 

Humidifying 

OFF 

Humidify with fan 

ON 

Humidifying 

FAN 

De-humidify only 

OFF 

OFF 

Dehumidifying 

De-humidify with fan 

ON 

FAN 

Dehumidifying 

Fan delay 

Once there is an output demand, the humidistat will first activate the fan, wait the required start delay time (CP12) 

and then activate the control output. This will ensure stable air for humidification or de-humidification. 
The control output will be switched off when the set point is reached. The fan keeps running until stop delay (CP13) 

has expired. This will ensure that no left over humidity remains in the device or its ducts.  

Controls Output 

Fan Output 

Demand 

CP12 

CP13 

Time [s] 

Содержание TCY-BH

Страница 1: ...tion The TCY BH is a stand alone electronic binary humidity stat The TCY BH features one internal humidity sensor one external NTC temperature sensor input and two binary outputs Relays A detailed par...

Страница 2: ...witching type AC switching power DO1 DO2 Relays 2 1 2 A 250VAC max fan power 300W Environment Operation Climatic conditions Temperature Humidity To IEC 721 3 3 class 3 K5 0 C 50 C 32 F 122 F 95 R H no...

Страница 3: ...umidify CP11 ON FAN CP10 2 If CP11 ON FAN Dehumidify N L Power In DO1 Relay 2A NTC 10k 1 2 G0 G 24VAC DC 5 6 Q23 Q24 N L 3 4 Q13 Q14 N L DO2 7 8 B1 M RT ext NTC10k TCY BH Power In DO1 Relay 2A NTC 10k...

Страница 4: ...er capacitor The time does not need to be re entered after a power failure Error messages The TCY BH may display the following error condition Err1 Humidity sensor faulty The humidity sensor is damage...

Страница 5: ...time schedule Pro1 Pro4 by using UP DOWN keys and pressing the ENTER key 1 Enable or disable the Pro1 time schedule Choose ON or OFF with the UP DOWN keys The following steps will only be accessible...

Страница 6: ...key will show CODE 2 Select a password using UP or DOWN buttons Select 009 in order to get access to the user parameters 241 for controls parameters Press OPTION after selecting the correct password 3...

Страница 7: ...cles and thus the wear on associated equipment 0 100 3 CP 08 Delay OFF Minimum running time MM SS Prevents a too short running cycle for the control output by setting a minimum running time 00 00 to 9...

Страница 8: ...point towards a defined TSET set point CP15 depending on the outdoor temperature Temperature setback becomes active when the outside temperature drops below the activation limit of temperature setback...

Отзывы: