Humidistat TCY-BH

 

 

Doc: 70-00-0142, V1.4, 20160912 

© Vector Controls GmbH, Switzerland 

Page 4 

Subject to alteration 

www.vectorcontrols.com 

Display and operation 

 

Operation mode and state indication 

 

Comfort (occupied) 

All control functions operating per set points. 

 

Economy (unoccupied): 

Set points shifted according to 

Parameters CP04.

 

Economy mode and setpoint shift may be disabled with UP04 

OFF 

Energy Hold Off 

Outputs are off, inputs monitored for alarm condition 

 

Fan active 

Fan is running 

 

Temperature setback 

Temperature setback is active and shifts setpoint 

Power failure 

All the parameters and set points are memorized and don’t need to be reentered. Depending on Parameter UP-03 the 

unit will remain switched off, switch on automatically or return to the operation mode it was in before the power failure. 

The deluxe version includes a real time clock with a 48h backup battery powered through a super capacitor. The time 

does not need to be re-entered after a power failure.  

Error messages 

The TCY-BH may display the following error condition:  

Err1:

 

Humidity sensor faulty. The humidity sensor is damaged or removed. Verify if sensing element! 

Err2:

 

External input for temperature setback missing or damaged.  

Left (POWER) 

Press < 2 sec.: Toggle STANDBY-
COMFORT mode or switch from OFF 
to ON 
Press > 2 sec.: Turn unit OFF. Text 
OFF displayed with current time 
(deluxe) temperature (standard) 
(Parameter setting: ENTER to 
select menu option, accept 

parameter change) 
 

Up  

Increment SET POINT  

(Parameter setting: 
SCROLL menu options 
and parameters) 
 

Down  

Decrement SET POINT  

(Parameter setting: SCROLL menu 
options and parameters) 
 

Mode 

Display of operation 

mode 

 
 

Large digits 

Display of input or parameter 
value. 

Indicators 

1 Temperature 

setback error 

Vertical bar 

Scrolls up = humidifying 
Scrolls down = dehumidifying 

Small digits 

Display of setpoint, clock or 

parameter number. 
 

Right (OPTION)  

Press < 2 sec.: Switch display 

Press > 2 sec.: Access time 
programs, change time.  

(Parameter setting: ENTER to 
select menu option, accept 
parameter change) 

Содержание TCY-BH

Страница 1: ...tion The TCY BH is a stand alone electronic binary humidity stat The TCY BH features one internal humidity sensor one external NTC temperature sensor input and two binary outputs Relays A detailed par...

Страница 2: ...witching type AC switching power DO1 DO2 Relays 2 1 2 A 250VAC max fan power 300W Environment Operation Climatic conditions Temperature Humidity To IEC 721 3 3 class 3 K5 0 C 50 C 32 F 122 F 95 R H no...

Страница 3: ...umidify CP11 ON FAN CP10 2 If CP11 ON FAN Dehumidify N L Power In DO1 Relay 2A NTC 10k 1 2 G0 G 24VAC DC 5 6 Q23 Q24 N L 3 4 Q13 Q14 N L DO2 7 8 B1 M RT ext NTC10k TCY BH Power In DO1 Relay 2A NTC 10k...

Страница 4: ...er capacitor The time does not need to be re entered after a power failure Error messages The TCY BH may display the following error condition Err1 Humidity sensor faulty The humidity sensor is damage...

Страница 5: ...time schedule Pro1 Pro4 by using UP DOWN keys and pressing the ENTER key 1 Enable or disable the Pro1 time schedule Choose ON or OFF with the UP DOWN keys The following steps will only be accessible...

Страница 6: ...key will show CODE 2 Select a password using UP or DOWN buttons Select 009 in order to get access to the user parameters 241 for controls parameters Press OPTION after selecting the correct password 3...

Страница 7: ...cles and thus the wear on associated equipment 0 100 3 CP 08 Delay OFF Minimum running time MM SS Prevents a too short running cycle for the control output by setting a minimum running time 00 00 to 9...

Страница 8: ...point towards a defined TSET set point CP15 depending on the outdoor temperature Temperature setback becomes active when the outside temperature drops below the activation limit of temperature setback...

Отзывы: