Humidistat TCY-BH
Doc: 70-00-0142, V1.4, 20160912
© Vector Controls GmbH, Switzerland
Page 3
Subject to alteration
www.vectorcontrols.com
Dimensions mm (inch)
Connection diagram
Description
:
Connections depend on parameter CP10 and CP11! (See page 10)
CP10
DO1
DO2
RT
CP10 = 0
Humidify
Dehumidify
Temperature input for
setback
NTC 10kΩ @ 25°C (77°F)
CP10 = 1
Humidify
CP11 = ON: FAN
CP10 = 2
If CP11 = ON: FAN
Dehumidify
N L
Power In
DO1
Relay 2A
NTC
10kΩ
1 2
G0 G
24VAC/DC
5 6
Q23 Q24
N
L
3 4
Q13 Q14
N
L
DO2
7 8
B1 M
RT ext.
NTC10k
Ω
TCY-BH
Power In
DO1
Relay 2A
NTC
10kΩ
1 2
N L
230VAC
4
Q24
N
DO2
7 8
B1 M
N L
3
Q14
N
RT ext.
NTC10k
Ω
TCY-BH-230
5 6
88 (3.5)
32 (1.2)
21
(0.8)
8
8
(
3
.5
)
5
8
(
2
.3
)
32 (1.2)
21
(0.8)
TCY-BH-230
Enlarged back part for TCY-BH-230
Space required in flush mounting box:
(H x W x D)
60 x 50 x 32mm (2.4 x 2.0 x 1.26 in.)
Distance for mounting screws:
Horizontal and vertical:
45 to 63mm (1.8 to 2.5 in.)
TCY-BH