background image

 

 

TLC3-FCR-T Engineering Manual

 

 

Doc: 70-00-0200, V3.1 Date: 20160411 

© Vector Controls GmbH, Switzerland 

Page 9 

Subject to alteration 

Input configuration 

FC 16 

External input:  

0 = No external input 

1 = External temperature sensor 

2 = Occupation sensor – Comfort / Economy 

3 = Occupation sensor – Comfort / Off 

4 = Heat / Cool changeover  

5 = Key card with alternative setpoint 

0…5 

FC 17 

Activation delay (Minutes) = the time the binary input 

needs to be open before economy/off mode is activated. 

0…255 min 

FC 18 

Auto-changeover limit heating FC16 = 4 

or economy setpoint in heating mode if FC16 = 5 

-40…60°C (160°F) 

16°C (61°F) 

FC 19 

Auto-changeover limit cooling FC16 = 4 

or economy setpoint in cooling mode if FC16 = 5 

-40…60°C (160°F) 

28°C (82°F) 

Run extension for fan at power off 

FC 20 

Fan run extension after active heating output 

0...255s 

60s 

FC 21 

Fan run extension after active cooling output 

0...255s 

60s 

Configuring the function of the external input 

 

FC16 = 0 

Input not used 

 

FC16 = 1 

External control input 

The external sensor is the control input. The internal sensor will 

be disabled.  

FC16 = 2 

Switching Economy and 

Comfort modes 

Economy (unoccupied) and Comfort (occupied) modes are 

controlled through an external contact by connecting the input 

through a dry contact to signal common. This function may be 

used together with key card switches for hotels or motion 

detectors for offices.

 

FC16 = 3 

Switching Energy Hold OFF 

and Comfort modes 

Opening the input will force the unit into the OFF operation 

mode. The operation mode cannot be overridden by using the 

terminal. Connecting the input to signal common returns 

control of the operation mode to the terminal. This function 

may be used as window contact to prevent loss of energy.  

FC16 = 4 

Heat – Cool changeover 

Switch heating and cooling mode based on supply media or 
outside temperature or binary contact. See below for further 

details.  

FC16 = 5 

Key card with alternative 

setpoint 

As with FC16 = 2, the key card function switches economy 

(unoccupied) and comfort (occupied) modes. Instead of using 

the setpoint shift, the setpoints in unoccupied mode are defined 

by parameter FC21 and FC22. 

 

Configuring auto changeover input if FC16 = 4:  

The auto changeover function automatically changes heating and cooling mode based on supply media 

temperature or outdoor temperature. The difference between the two is in the values of the changeover limits 

FC18 and FC19. See table below for recommended settings. 

Heating and cooling may be as well changed by an open contact switched to signal ground. Note: all signal ground 

levels of involved controllers must be the same in case more than one controller is switched.  

 

Recommended settings for FC18 and FC19: 

Change over mode FC16=4 

Relation FC18 to 
FC19 

Example FC18 

Example: FC19 

Supply media 

FC18 > FC19 

25°C (77F) 

18°C (64F) 

Outside temperature 

FC18 < FC19 

15°C (59F) 

25°C (77F) 

Dry contact: Heating if contact closed 

FC18 > FC19 

25°C (77F) 

15°C (59F) 

Dry contact: Cooling if contact closed 

FC18 < FC19 

15°C (59F) 

25°C (77F) 

 

Run extension for fan: 

This keeps the fan running until the defined time runs out when switching the unit off or deactivating the valve. 

The idea is to prevent condensation on the cooling coil or triggering the overheat fuse on electrical reheat devices. 

 

 
 

 

Содержание 40-10 0114

Страница 1: ...tems o radiator control chilled ceiling Simple individual room control for hotel rooms meeting rooms etc PWM or On Off Control of 2 spring return valves or 3 point on off or floating control of one 3...

Страница 2: ...721 3 2 and IEC 721 3 1 class 3 K3 and class 1 K3 25 C 70 C 13 F 158 F 95 R H non condensing class 2M2 Standards conformity EMC Directive Low Voltage Directive 2004 108 EC 2006 95 EC Product standards...

Страница 3: ...at the jumpers are set correctly 4 Slide the two latches located on the top of the front part into the hooks at the upper side of the mounting plate 5 Carefully lower the front part until the intercon...

Страница 4: ...ft once the temperature reaches 10 C 50 F Frost protection display will remain until a button is pressed Frost protection can be enabled disabled using user parameter UP 09 Toggle C F display with one...

Страница 5: ...ess UP DOWN to step through available options d1 7 d1 6 d1 5 d6 7 day1 day2 day3 day4 day5 day6 day7 Day 1 stands for Monday day 2 for Tuesday and so forth Press OPTION to save day selection Pro1 d1 7...

Страница 6: ...oop may be changed Set point range is 15 to 30 C Changing of fan speeds Repeatedly pressing the fan speed button steps through low medium high and automatic fan speeds Automatic fan speed will not be...

Страница 7: ...ontrol of fan speeds ON OFF ON Enabled UP 03 Function of advanced mode long press right key 0 disabled 1 access to heat cool fan only change 2 access to clock settings and time programs 3 access to he...

Страница 8: ...rence between switching on and switching off A small hysteresis will increase the number of switching cycles and thus the wear on fan and relays contacts 0 10 0 C 20 0 F 0 5 C 1 F FC 08 Mold Protectio...

Страница 9: ...verridden by using the terminal Connecting the input to signal common returns control of the operation mode to the terminal This function may be used as window contact to prevent loss of energy FC16 4...

Страница 10: ...TLC3 FCR T Engineering Manual Doc 70 00 0200 V3 1 Date 20160411 Vector Controls GmbH Switzerland Page 10 Subject to alteration Notes...

Отзывы: