TLC3-FCR-T Engineering Manual

 

 

Doc: 70-00-0200, V3.1 Date: 20160411 

© Vector Controls GmbH, Switzerland 

Page 3 

Subject to alteration 

Mounting location 

 

Install the controller on an easy accessible interior wall, approx. 1.5 m above the floor in an area of average 

temperature. 

 

Avoid direct sunlight or other heat sources, e.g. the area above radiators and heat emitting equipment.  

 

Avoid locations behind doors, outside walls and below or above air discharge grills and diffusers.  

 

Location of mounting is less critical if external temperature sensors are used. 

Installation 

1.

 

Connect the wires to be connected to the terminals of the power case according to wiring diagram 

2.

 

Install the mounting plate to the flush mounting box. Make sure that the nipple with the front holding screw is 

facing to the ground. Make sure the mounting screw heads do not stand out more than 5 mm (0.2”) off the 

surface of the mounting plate.  

3.

 

Ensure that the jumpers are set correctly.  

4.

 

Slide the two latches located on the top of the front part into the hooks at the upper side of the mounting plate.  

5.

 

Carefully lower the front part until the interconnector reaches the mounting-plate. Continue pressing in a gentle 

way until the front part is fully connected. While inserting the connectors, a slight resistance can be felt. This is 

normal. Do not use excessive force!  

6.

 

With a Philips-type screw driver of size #2, carefully tighten the front holding screw to secure the front part to 

the mounting plate. This screw is located on the front lower side of the unit. There is no need to tighten the 

screw too much. 

 

Wiring Diagram 

 

Description:  

Power supply:  

0V Neutral 

Power supply:  

230VAC 

Y1 

Binary output 230V AC:  

Fan speed low 

Y2 

Binary output 230V AC:  

Fan speed medium 

Y3 

Binary output 230V AC:  

Fan speed high 

Y4 

Binary output 230V AC:  

Valve (Heating or cooling) 

 

X1

 

External input: 

NTC 10kΩ @ 25°C (77°F) or open contact to SGND 

Signal common:  

0 potential for inputs 

 

X

T INT 

0V 

230V AC 

 

TLC3-FCR-T 

X1 

X

T EXT

  

IN 

 

SGND 

 

Y1 

Fan 

Low 

Y2 

Fan 

Med 

Y3 

Fan 

High 

Y4 

Valve 

Содержание 40-10 0114

Страница 1: ...tems o radiator control chilled ceiling Simple individual room control for hotel rooms meeting rooms etc PWM or On Off Control of 2 spring return valves or 3 point on off or floating control of one 3...

Страница 2: ...721 3 2 and IEC 721 3 1 class 3 K3 and class 1 K3 25 C 70 C 13 F 158 F 95 R H non condensing class 2M2 Standards conformity EMC Directive Low Voltage Directive 2004 108 EC 2006 95 EC Product standards...

Страница 3: ...at the jumpers are set correctly 4 Slide the two latches located on the top of the front part into the hooks at the upper side of the mounting plate 5 Carefully lower the front part until the intercon...

Страница 4: ...ft once the temperature reaches 10 C 50 F Frost protection display will remain until a button is pressed Frost protection can be enabled disabled using user parameter UP 09 Toggle C F display with one...

Страница 5: ...ess UP DOWN to step through available options d1 7 d1 6 d1 5 d6 7 day1 day2 day3 day4 day5 day6 day7 Day 1 stands for Monday day 2 for Tuesday and so forth Press OPTION to save day selection Pro1 d1 7...

Страница 6: ...oop may be changed Set point range is 15 to 30 C Changing of fan speeds Repeatedly pressing the fan speed button steps through low medium high and automatic fan speeds Automatic fan speed will not be...

Страница 7: ...ontrol of fan speeds ON OFF ON Enabled UP 03 Function of advanced mode long press right key 0 disabled 1 access to heat cool fan only change 2 access to clock settings and time programs 3 access to he...

Страница 8: ...rence between switching on and switching off A small hysteresis will increase the number of switching cycles and thus the wear on fan and relays contacts 0 10 0 C 20 0 F 0 5 C 1 F FC 08 Mold Protectio...

Страница 9: ...verridden by using the terminal Connecting the input to signal common returns control of the operation mode to the terminal This function may be used as window contact to prevent loss of energy FC16 4...

Страница 10: ...TLC3 FCR T Engineering Manual Doc 70 00 0200 V3 1 Date 20160411 Vector Controls GmbH Switzerland Page 10 Subject to alteration Notes...

Отзывы: