Control configuration  

Identifying the firmware version 

The parameters and functionality of controller depend on its firmware revision. It is therefore important to use a 

matching product version and parameter set. The firmware version is shown on the large LCD digits when pressing UP 

and DOWN buttons for more than 3 seconds simultaneously.  

Control Parameters (Access code: 241) 

Warning! Only experts should change these settings! See user parameters for login procedure.  

Parameter 

Description 

Range 

Standard 

FC 00 

Minimum setpoint limit in Heating mode 

-40…60°C (160°F) 

16°C (61°F) 

FC 01 

Maximum setpoint limit in Heating mode 

-40…60°C (160°F) 

24°C (75°F) 

FC 02 

Minimum setpoint limit in Cooling mode 

-40…60°C (160°F) 

18°C (64°F) 

FC 03 

Maximum setpoint limit in Cooling mode 

-40…60°C (160°F) 

30°C (86°F) 

Controls configuration 

FC 04 

Economy (unoccupied) Mode temperature shift: 
The comfort (occupied) setpoint is shifted by the value 

set with parameter. If heating is active the comfort 

setpoint will be decreased, if cooling is active, the 

setpoint will be increased. (Enable with UP06.) 

0…10.0°C (20.0°F) 

5.0°C (10°F) 

FC 05 

Switching Span Heating 

0…10.0°C (20.0°F) 

1.5°C (3.0°F) 

FC 06 

Switching Span Cooling 

0…10.0°C (20.0°F) 

1.0°C (2.0°F) 

FC 07 

Switching Hysteresis is the difference between switching 
on and switching off. A small hysteresis will increase the 

number of switching cycles and thus the wear on fan and 

relays contacts. 

0…10.0°C (20.0°F) 

0.5°C (1°F) 

FC 08 

Mold Protection:  

In mold protection, the fan keeps running independent of 

temperature as long as the unit is switched on. 

ON, OFF 

OFF 

FC 09 

Switching delay min running time of fan speed 

0…255 s 

10s 

FC 10 

Switching delay min stopping  time of fan speed 

0…255 s 

10s 

FC 11 

Control option:  
0 = Cooling only 

1 = Heating only 

2 = 2-pipe system 

0…2 

-W1: = 0 

-W2: = 1 

Default: = 2 

Control Configuration for PWM mode 

FC 12 

P – band heating X

PH

 

0-10.0°C (20.0°F) 

2.0°C (4.0°F) 

FC 13 

P – band cooling X

PC

 

0-10.0°C (20.0°F) 

2.0°C (4.0°F) 

 

Proportional control

 

(P-band)  

The proportional control function calculates the output based on the difference between setpoint and measured 

value. The proportional band (P-band) defines the difference between setpoint and measured value which will 

result in a 100% output. Setting the proportional band to 0 disables proportional control.  

 

Output configuration 

FC 14 

PWM cycle time heating, 0 disables PWM mode 

0…100 min 

FC 15 

PWM cycle time cooling, 0 disables PWM mode 

0…100 min 

 

Pulse With Modulation (PWM)  

In PWM mode the digital output will be switched on/off once per cycle. The on and off times are calculated 

according to the control sequence. It is not recommended to use cycle times below 10 minutes as the lifetime of 

the relays will be shortened with frequent switching. For PWM applications requiring cycle times below 100 

seconds we recommend using TLC3-FCR-2 with TRIAC outputs 

 

 

 

Содержание 40-10 0114

Страница 1: ...tems o radiator control chilled ceiling Simple individual room control for hotel rooms meeting rooms etc PWM or On Off Control of 2 spring return valves or 3 point on off or floating control of one 3...

Страница 2: ...721 3 2 and IEC 721 3 1 class 3 K3 and class 1 K3 25 C 70 C 13 F 158 F 95 R H non condensing class 2M2 Standards conformity EMC Directive Low Voltage Directive 2004 108 EC 2006 95 EC Product standards...

Страница 3: ...at the jumpers are set correctly 4 Slide the two latches located on the top of the front part into the hooks at the upper side of the mounting plate 5 Carefully lower the front part until the intercon...

Страница 4: ...ft once the temperature reaches 10 C 50 F Frost protection display will remain until a button is pressed Frost protection can be enabled disabled using user parameter UP 09 Toggle C F display with one...

Страница 5: ...ess UP DOWN to step through available options d1 7 d1 6 d1 5 d6 7 day1 day2 day3 day4 day5 day6 day7 Day 1 stands for Monday day 2 for Tuesday and so forth Press OPTION to save day selection Pro1 d1 7...

Страница 6: ...oop may be changed Set point range is 15 to 30 C Changing of fan speeds Repeatedly pressing the fan speed button steps through low medium high and automatic fan speeds Automatic fan speed will not be...

Страница 7: ...ontrol of fan speeds ON OFF ON Enabled UP 03 Function of advanced mode long press right key 0 disabled 1 access to heat cool fan only change 2 access to clock settings and time programs 3 access to he...

Страница 8: ...rence between switching on and switching off A small hysteresis will increase the number of switching cycles and thus the wear on fan and relays contacts 0 10 0 C 20 0 F 0 5 C 1 F FC 08 Mold Protectio...

Страница 9: ...verridden by using the terminal Connecting the input to signal common returns control of the operation mode to the terminal This function may be used as window contact to prevent loss of energy FC16 4...

Страница 10: ...TLC3 FCR T Engineering Manual Doc 70 00 0200 V3 1 Date 20160411 Vector Controls GmbH Switzerland Page 10 Subject to alteration Notes...

Отзывы: