background image

 
 

Chapter 1 

 

Frigoboat Systems 

 

   

A Frigoboat refrigeration system consists of the following components: 

 
(1) 

 A compressor/condensing unit that is either: 

 

 

Air cooled – Paris 35F, Capri 35F, Capri 50F 

 

 

Pumped-water cooled – W35F, W50F (with pump) 

 

 

Keel cooled – K35F, K50F (with keel cooler) 

 

 

Keel plus Air Cooled - Paris 35F, Capri 35F, or Capri 50F with Keel Cooler 

 
(2) 

An electronic controller connected to and installed on the compressor. 

 

 
(3)  Either a mechanical thermostat dedicated for either refrigerator or freezer or a Coastal MK 3 

digital thermostat/thermometer 

 
(5)  An aluminum or stainless steel evaporator plate 
 
(6)  A water pump (For W35F or W50F only) 
 
(7)  A Keel Cooler. Standard with K35F and K50F models, optional with Air Cooled models. 

 

APPLICATION 

 
Frigoboat refrigeration systems are designed to preserve foodstuffs, drinks, and other consumables 
intended for human consumption, and at normal refrigerator and freezer temperatures. Any use 
other than that specified above invalidates the warranty and releases Veco NA LLC of any liability 
for consequent damage, failure, malfunction, injury, illness, or death. 

----------------------------------------------------- 

 

Chapter 2

 

 

 Paris 35F, Capri 35F, Capri 50F - Air cooled

 

 
These units are designed to be mounted with compressor right way up on a horizontal surface in areas 
where they will not be susceptible to physical or water damage, but accessible for service. They 
require good ventilation, preferably expelling the heated air to another location by attaching a flexible 
duct of not more than 6' in length to the duct ring on the unit. A duct kit is available for Capri 35 and 
Capri 50 models. Do not add any filter type material anywhere in the air flow. 
 
If air is required to be drawn 

into

 the unit from another area, the fan may be reversed by removing the 

housing and re-mounting the fan in the opposite orientation. 

Reversing the fan leads does not make 

the fan run in reverse, and the incorrect polarity will result in the fan not operating.

 

 
There should be adequate ventilation to allow cool air to enter the condenser, and precautions 
made to prevent the heated expelled air from being drawn back in.

 The temperature of the air 

entering the condenser determines the efficiency of the system. Re-circulating the heated air back into 
the condenser in a sealed or poorly ventilated cabinet will result in poor system performance. Poor 
system performance will also result from air being drawn in from a heated space, i.e. an engine room. 

Содержание Frigoboat Capri 35F

Страница 1: ...s Air Cooled Pumped Water Cooled Keel Cooled and Keel plus Air Cooled Systems using Secop formally Danfoss BD 35 or BD 50 compressors It is important to read this manual thoroughly before installing a...

Страница 2: ...it or an Air Add On air cooled condenser is installed together with a Keel Cooler ensure that the fan is operated only when the boat is out of the water and then switched off when the boat is launched...

Страница 3: ...Capri 35F Capri 50F Air cooled These units are designed to be mounted with compressor right way up on a horizontal surface in areas where they will not be susceptible to physical or water damage but...

Страница 4: ...ll deliver 12v even if the system is connected to a 24v supply Full wiring instructions are included with the compressor If more than one W35 or W50 is sharing a single water pump they must be plumbed...

Страница 5: ...ion of the transom that is below the waterline when at rest Keep the two tubes from the Keel Cooler separate from each other and do not insulate them It is extremely important to orientate the cylindr...

Страница 6: ...control running at 2000 RPM All others must have either a manually adjustable compressor speed controller like a Speed Board or alternatively an automatic smart speed control such as the Merlin II Sma...

Страница 7: ...to the controller there may be a delay of up to 30 seconds before the compressor starts Note 2 If initial power is applied that is above the low voltage threshold but below the cut in voltage value se...

Страница 8: ...els in the evaporator Never attempt to bend a plate downwards over a pipe as damage may result The area to be bent should be warmed with a hair dryer or heat gun to approximately 200 F before bending...

Страница 9: ...lastic plate on the evaporator so that it lays in the special grooves of the plastic plate Finish by tightening the clamping screw If using the Coastal MK3 digital thermostat the sensor mounts on the...

Страница 10: ...refully coiled up and secured out of the way to avoid damage When securing the sensing tube make sure contact is made only with the evaporator at the point where it is attached under the plastic mount...

Страница 11: ...top of the barrier 1 should be sufficient or 3 or more holes of the same size as the one behind the spillover fan All other holes gaps etc in the barrier must be completely sealed including drains 8...

Страница 12: ...talled until the very last moment when you are ready to connect the system together Once the dust caps have been removed it is imperative that the exposed components and surfaces be kept free of dust...

Страница 13: ...tion Use either a breaker or fast blow fuse with 15 amp rating for a 12v supply or 7 5 amp for 24v 10 4 Connections Power Connect the power supply to the controller on the top two terminals using slip...

Страница 14: ...factory installed on the terminals marked F Black or Blue and Red If the wires are reversed the fan will not run The K50F and W50F models have a small oil cooler fan installed Full instructions are i...

Страница 15: ...oller or compressor to be faulty Controller can be removed by unscrewing the retaining screw or by levering the plastic case over the screw head 11 1 Compressor not running no start attempt Probable c...

Страница 16: ...ty or inadequate power supply Most likely Monitor the supply voltage at the power terminals on the controller before during and after start attempts to ensure that it does not fall below threshold lev...

Страница 17: ...ng in others the system may be low on refrigerant or overcharged Call Veco NA for advice or go to www veco na com Technical Information 7 Drain left unplugged If your icebox is equipped with a drain i...

Страница 18: ...lation 11 5 Excessive frost build up Note This is the result of moist air being allowed to enter the box Problems are compounded when cold dense air leaks from the lower area of the box through an ope...

Страница 19: ...cation Acts of God or service by personnel other than those pre authorized by the Company Damage failure or malfunction resulting from inadequate or faulty power supply to the system or improper fault...

Отзывы: