background image

 
 

Chapter 7 

 

Mechanical Thermostat for H, B, and F Evaporators 

(See separate instruction sheet for Coastal MK3) 

 

7:1 

Refrigerator & Freezer thermostats

 

There are two different thermostats for different applications. The refrigerator version is mounted in a 
white housing and is designed to be used where the evaporator is mounted in an icebox that is intended 
to be kept at refrigerator temperatures. If the evaporator is of the H- or B-type and is correctly sized, a 
refrigerator mechanical thermostat is used and this ensures that the interior portion of these evaporators 
will be kept at freezer temperatures. 

The freezer version is mounted in a blue housing and must be used where the evaporator is mounted in 
a space that is intended to be all at freezer temperatures. 

If an existing icebox is divided with an insulated barrier, a spillover system can be employed whereby 
the evaporator is mounted in the freezer compartment, and a thermostatically controlled fan, mounted 
on the refrigerator side of the barrier, draws air from the freezer to keep the refrigerator section at the 
desired temperature. A gap or holes at the top of the barrier allow air to return to the freezer.  
 

7:2 

Mounting

 

The mechanical thermostat can be mounted either inside the icebox, or in an alternative location that is 
within the scope of the sensing tube. If the thermostat is mounted inside the box make sure that liquids 
or condensation cannot flow down the shaft and into the mechanism by positioning the housing so that 
the shaft exits either on the bottom or the side. The Frigoboat logo will be the right way up if the 
thermostat is mounted correctly. Markings can be made on the perimeter of the knob to assist in 
determining the setting. Do not mount on the ceiling of the box. The sensing tube controls the 
thermostat by the pressure of the gas it contains and must not be kinked, broken, or cut.  Any excess 
tubing may be carefully coiled up and secured out of the way to avoid damage. 
 
When securing the sensing tube, make sure contact is made only with the evaporator at the point where 
it is attached under the plastic mounting plate and that it does not touch any part of the aluminum or 
copper tubing. If necessary, the tube can be protected with small-bore plastic tubing, either by sliding 
it on prior to attaching to the evaporator or by slitting it along its length and feeding it over the sensing 
tube. Run the cable together with the copper lines to the compressor /condensing unit. Care must be 
taken to ensure that the sensing tube does not come into contact with any electrical component either 
inside or outside the icebox. There is an insulating cover over the most exposed wire terminal and 
connector inside the plastic thermostat housing. An inspection must be made before mounting, to 
ensure that the entire terminal and connector is covered and that no metal parts are exposed. Confirm, 
before mounting the thermostat, that the capillary tube is not in contact with any wire terminal, 
connector, or bare wire. If the sensing tube needs to be bent within the confines of the plastic 
thermostat housing, it must be done with great care, heeding the warnings above.   
 

7:3 

Operation

 

The thermostat knob is marked from 0 to 7 with 7 being the coldest setting. From this position the 
knob can be rotated counter-clockwise to setting 1, which is the warmest. On initial system start-up, it 
is recommended that you set the thermostat to number 4, letting the system run through a few cycles 
while monitoring box temperature before any adjustments are made. Once the right setting is found for 
your application there should be no need for the thermostat to be adjusted again. If it is not possible to 
see the numbers on the dial, it is recommended to reproduce them on the perimeter. 
Setting the knob to the 0 position will turn the system off. It is recommended that the system 

not

 be 

turned off and on from the thermostat. To turn the system off and on, use a panel-mounted breaker or 
install a switch in line with the power supply. 

Содержание Frigoboat Capri 35F

Страница 1: ...s Air Cooled Pumped Water Cooled Keel Cooled and Keel plus Air Cooled Systems using Secop formally Danfoss BD 35 or BD 50 compressors It is important to read this manual thoroughly before installing a...

Страница 2: ...it or an Air Add On air cooled condenser is installed together with a Keel Cooler ensure that the fan is operated only when the boat is out of the water and then switched off when the boat is launched...

Страница 3: ...Capri 35F Capri 50F Air cooled These units are designed to be mounted with compressor right way up on a horizontal surface in areas where they will not be susceptible to physical or water damage but...

Страница 4: ...ll deliver 12v even if the system is connected to a 24v supply Full wiring instructions are included with the compressor If more than one W35 or W50 is sharing a single water pump they must be plumbed...

Страница 5: ...ion of the transom that is below the waterline when at rest Keep the two tubes from the Keel Cooler separate from each other and do not insulate them It is extremely important to orientate the cylindr...

Страница 6: ...control running at 2000 RPM All others must have either a manually adjustable compressor speed controller like a Speed Board or alternatively an automatic smart speed control such as the Merlin II Sma...

Страница 7: ...to the controller there may be a delay of up to 30 seconds before the compressor starts Note 2 If initial power is applied that is above the low voltage threshold but below the cut in voltage value se...

Страница 8: ...els in the evaporator Never attempt to bend a plate downwards over a pipe as damage may result The area to be bent should be warmed with a hair dryer or heat gun to approximately 200 F before bending...

Страница 9: ...lastic plate on the evaporator so that it lays in the special grooves of the plastic plate Finish by tightening the clamping screw If using the Coastal MK3 digital thermostat the sensor mounts on the...

Страница 10: ...refully coiled up and secured out of the way to avoid damage When securing the sensing tube make sure contact is made only with the evaporator at the point where it is attached under the plastic mount...

Страница 11: ...top of the barrier 1 should be sufficient or 3 or more holes of the same size as the one behind the spillover fan All other holes gaps etc in the barrier must be completely sealed including drains 8...

Страница 12: ...talled until the very last moment when you are ready to connect the system together Once the dust caps have been removed it is imperative that the exposed components and surfaces be kept free of dust...

Страница 13: ...tion Use either a breaker or fast blow fuse with 15 amp rating for a 12v supply or 7 5 amp for 24v 10 4 Connections Power Connect the power supply to the controller on the top two terminals using slip...

Страница 14: ...factory installed on the terminals marked F Black or Blue and Red If the wires are reversed the fan will not run The K50F and W50F models have a small oil cooler fan installed Full instructions are i...

Страница 15: ...oller or compressor to be faulty Controller can be removed by unscrewing the retaining screw or by levering the plastic case over the screw head 11 1 Compressor not running no start attempt Probable c...

Страница 16: ...ty or inadequate power supply Most likely Monitor the supply voltage at the power terminals on the controller before during and after start attempts to ensure that it does not fall below threshold lev...

Страница 17: ...ng in others the system may be low on refrigerant or overcharged Call Veco NA for advice or go to www veco na com Technical Information 7 Drain left unplugged If your icebox is equipped with a drain i...

Страница 18: ...lation 11 5 Excessive frost build up Note This is the result of moist air being allowed to enter the box Problems are compounded when cold dense air leaks from the lower area of the box through an ope...

Страница 19: ...cation Acts of God or service by personnel other than those pre authorized by the Company Damage failure or malfunction resulting from inadequate or faulty power supply to the system or improper fault...

Отзывы: