background image

 
 

 

 

Sensor of Mechanical 
Thermostat not in good thermal 
contact with evaporator at 
designed location. 

The free end of the Mechanical Thermostat sensor must be in 
good thermal contact with the evaporator at the point where 
the black plastic clamp is situated. Not attaching the sensor, 
or attaching at somewhere other than the designed location 
will result in undesirable box temperatures.  

 

 

Poor spillover system 
construction 

If you are running the evaporator as a freezer and cooling an 
adjoining refrigerator compartment with spillover air, there 
must be an adequate thermal barrier between the two. It also 
must be completely sealed down the sides and along the 
bottom to prevent unwanted air-flow. Temperatures in the 
refrigerator side should be controlled either with trial-and-
error convection holes, or a thermostatically controlled fan, 
(Spillover Fan/Thermostat Kit, PN E26200). Two apertures 
are necessary, one high and one mid-height for adequate air 
circulation.   

 
 

11:5  

Excessive frost build-up

 

 

Note 

This is the result of moist air being allowed to enter the box. Problems are compounded when 
cold, dense air leaks from the lower area of the box through an open drain or weak door seal 
and is replaced by warm, humid air being drawn in elsewhere. 

 

 

 

 

        Probable cause 

                                 Action 

 

 

Drains and holes not plugged 

Make sure all drains and holes in the floor and walls of the 
box are sealed. 

 

 

Circulating fan 

If a small fan is used to circulate air in the box, make sure 
that it is not too powerful, and that cold air is not escaping 
from a door/lid seal. This could force cold air out of the 
refrigerator box, and the freezer then has to draw air in from 
a weak seal to replace it.   

 

 

Poor or damaged door/lid seals 

Check seals and replace if necessary. A good seal will grip a 
$1 bill when inserted between the seal and door/lid when 
closed. A front opening door/top opening lid combination 
with poor seals is likely to result in excessive frost build-up 
on the evaporator and cause extended run times. To 
determine leaking seals, apply masking tape to suspect areas 
after defrosting, and then check after several days for frost 
build-up. 

 

Содержание Frigoboat Capri 35F

Страница 1: ...s Air Cooled Pumped Water Cooled Keel Cooled and Keel plus Air Cooled Systems using Secop formally Danfoss BD 35 or BD 50 compressors It is important to read this manual thoroughly before installing a...

Страница 2: ...it or an Air Add On air cooled condenser is installed together with a Keel Cooler ensure that the fan is operated only when the boat is out of the water and then switched off when the boat is launched...

Страница 3: ...Capri 35F Capri 50F Air cooled These units are designed to be mounted with compressor right way up on a horizontal surface in areas where they will not be susceptible to physical or water damage but...

Страница 4: ...ll deliver 12v even if the system is connected to a 24v supply Full wiring instructions are included with the compressor If more than one W35 or W50 is sharing a single water pump they must be plumbed...

Страница 5: ...ion of the transom that is below the waterline when at rest Keep the two tubes from the Keel Cooler separate from each other and do not insulate them It is extremely important to orientate the cylindr...

Страница 6: ...control running at 2000 RPM All others must have either a manually adjustable compressor speed controller like a Speed Board or alternatively an automatic smart speed control such as the Merlin II Sma...

Страница 7: ...to the controller there may be a delay of up to 30 seconds before the compressor starts Note 2 If initial power is applied that is above the low voltage threshold but below the cut in voltage value se...

Страница 8: ...els in the evaporator Never attempt to bend a plate downwards over a pipe as damage may result The area to be bent should be warmed with a hair dryer or heat gun to approximately 200 F before bending...

Страница 9: ...lastic plate on the evaporator so that it lays in the special grooves of the plastic plate Finish by tightening the clamping screw If using the Coastal MK3 digital thermostat the sensor mounts on the...

Страница 10: ...refully coiled up and secured out of the way to avoid damage When securing the sensing tube make sure contact is made only with the evaporator at the point where it is attached under the plastic mount...

Страница 11: ...top of the barrier 1 should be sufficient or 3 or more holes of the same size as the one behind the spillover fan All other holes gaps etc in the barrier must be completely sealed including drains 8...

Страница 12: ...talled until the very last moment when you are ready to connect the system together Once the dust caps have been removed it is imperative that the exposed components and surfaces be kept free of dust...

Страница 13: ...tion Use either a breaker or fast blow fuse with 15 amp rating for a 12v supply or 7 5 amp for 24v 10 4 Connections Power Connect the power supply to the controller on the top two terminals using slip...

Страница 14: ...factory installed on the terminals marked F Black or Blue and Red If the wires are reversed the fan will not run The K50F and W50F models have a small oil cooler fan installed Full instructions are i...

Страница 15: ...oller or compressor to be faulty Controller can be removed by unscrewing the retaining screw or by levering the plastic case over the screw head 11 1 Compressor not running no start attempt Probable c...

Страница 16: ...ty or inadequate power supply Most likely Monitor the supply voltage at the power terminals on the controller before during and after start attempts to ensure that it does not fall below threshold lev...

Страница 17: ...ng in others the system may be low on refrigerant or overcharged Call Veco NA for advice or go to www veco na com Technical Information 7 Drain left unplugged If your icebox is equipped with a drain i...

Страница 18: ...lation 11 5 Excessive frost build up Note This is the result of moist air being allowed to enter the box Problems are compounded when cold dense air leaks from the lower area of the box through an ope...

Страница 19: ...cation Acts of God or service by personnel other than those pre authorized by the Company Damage failure or malfunction resulting from inadequate or faulty power supply to the system or improper fault...

Отзывы: