3

* Parameters ALFA(NET) 52

Para-
Meter

Description Parameter

Range

Standard
value

01

02

03

Function relay 1

Function relay 2

Function relay 3

1=Cool
2=Heat
3=Alarm
1=Cool
2=Heat
3=Alarm
1=Cool
2=Heat
3=Alarm

1

1

3

05
06

Offset temperature sensor-1
Offset temperature sensor-2

-15..+15

C

-15..+15

C

0
0

10
11
12
13
14
15

Switching differential relay 1
Set point offset relay 1
Switching differential relay 2
Set point offset relay 2
Switching differentia relay 3
Set point offset relay 3

0.1..15
-15..+15
0.1..15
-15..+15
0.1..15
-15..+15

0.5

0

0.5

0

0.5

0

20
21
22

23
24

Switch on delay cooling
Switch off delay cooling
Parameter 20/21 in Sec. or Min.

Minimum on-time cooling
Minimum off-time cooling

0..99
0..99
0=Seconds
1=Minutes
0..99 Minutes
0..99 Minutes

0
0
0

0
0

25
26

Minimum set point
Maximum set point

0..+100

C

0..+100

C

0

+100

30

31
32
33
34

35

36
37
38
39

40

41

42

Alarm type thermostat-1 (to set point)

Minimum alarm set point-1
Maximum alarm set point-1
Time delay minimum alarm-1
Time delay maximum alarm-1

Alarm type thermostat-2 (to set point)

Minimum alarm set point-2
Maximum alarm set point-2
Time delay minimum alarm-2
Time delay maximum alarm-2

Relay function alarm relay

Reset alarm relay after recovering alarm

Reset alarm relay after manual reset

0= None
1= Absolute
2= Relative
0..+100

C

0..+100

C

0..99 min.
0..99 min.

0= None
1= Absolute
2= Relative
0..+100

C

0..+100

C

0..99 min.
0..99 min.

0= Watch
1= Control
0= No
1= Yes
0= No
1= Yes

1

0

+100

0
0

1

0

+100

0
0

0

0

0
0

45
46
47

Start up delay after power failure
Forced relay-1 on at sensor-1 failure
Forced relay-2(,3) on at sensor-2
 failure

0..99 Minutes
0= No, 1=Yes
0= None 
2= Relay-2 on
3= Relay-3 on

0
0

90
95
96
97
98
99

Network number
Software version
Production year
Production week
Serial number (x1000)
Serial number (units)

1..255
0..255
00..99
1..52
0..255
0..999

1
0
0
1
0
0