2

* Status of the Relays.

By pushing the 

MODE

 key the display shows the status of the relays. Each display segment shows

the status of the relay output, showing 0=off and 1=on. The code 110 means relay 1 and 2 are on
and relay 3 is off.

* Setting internal parameters.

Next to the adjustment of the set point, internal settings can be made like differential, sensor offset,
set point range and the functions of the thermostat.
Push the 

DOWN

 key more than 10 seconds, to enter the 'Internal Programming Menu'. In the left

display the upper and lower segment are blinking. Over the 

UP

 and 

DOWN

 keys the required

parameter can be selected (see table for the parameters).
If the required parameter is selected, the value can be read-out by pushing the 

SET

 key. Pushing

the 

UP

 or 

DOWN

 key to change the value of this parameter.

If after 20 seconds no key is pushed, the 

ALFA(NET) 52

 changes to the normal operation mode. 

* Adjustment sensors.

Sensor-1 can be adjusted by using the Sensor Offset parameter 05 and Sensor-2 can be adjusted
by using the Sensor Offset parameter 06. Indicates a Sensor e.g. 2

C to much, the according

Sensor Offset has to be decreased with 2

C.

* Error messages.

In the display of the 

ALFA(NET) 52

 the following error messages can appear:

Lo1

- Minimum alarm thermostat-1.

Solution E1,E2:

Hi1

- Maximum alarm thermostat-1.

- Check if the sensor is connected correctly.

Lo2

- Minimum alarm thermostat-2.

- Check sensor (1000

 at 25

C).

Hi2

- Maximum alarm thermostat-2.

- Replace sensor.

E1

- Sensor-1 failure.

E2

- Sensor-2 failure.

Solution EEE:

EEE

- Settings are lost.

- Reprogram the settings.

-L-

- In case of sensor short-circuit the display alternates between error-code 

E..

  and 

-L-

, as indication for a short-circuit sensor.

-H-

- In case of open-circuit sensor the display alternates between error-code 

E..

 

 and 

-H-

, as indication for  a open circuit sensor.

Reset Alarm.

 When an error-messages appears it can be reset by pushing the 

SET

 key. The

function of this key depends on parameter P42.

* Technical data ALFA(NET) 52.

Type

: ALFA(NET) 52 Double thermostat (Rail-mounting)

Range

: 0/+100

C per 0,1

C

Supply

: 230Vac 50/60Hz (-5/+10%)

Readout

: 3-digit 7-segment display

Relays

: Ry1= SPST(NO)

250V/8A(cos 

=1) or 250V/5A (cos 

=0.4)

  Ry2= SPST(NO)

250V/8A (cos 

=1) or 250V/5A (cos 

=0.4)

  Ry3= SPDT(NO/NC)

250V/8A (cos 

=1) or 250V/5A (cos 

=0.4)

  Relays have one common (C).

Control

: By push buttons on front.

Front

: Polycarbonate

Sensors

: 2x SM 811/2m (PTC 1000

/25

C).

Communication

: RS 485 Network (2xtwisted pair shielded) only at ALFANET model.

Dimensions

: 90 x 71 x 58mm (HWD)

Panel cutout

: 46 x 71mm (HW) at front mounting

Accuracy

: ± 0,5% of the range.

- Provided with memory protection during power failure.
- Connections with screw terminals on the back side.
- Equipped with sensor failure detection.
- Special versions on request available.