Installation, Operating & Maintenance Instructions
Series 650 DN 350 (I.D. 14”), CC-Link
VAT Vakuumventile AG, CH-9469 Haag, Switzerland
Tel +41 81 771 61 61 Fax +41 81 771 48 30 [email protected] www.vatvalve.com
286241EA
2010-10-11
65/86
GENERAL STATUS bitmap table:
Bit
Description
0
FIELDBUS DATA VALID
0 = Valve is not ready for communication (has not received the rising edge of "Initial Data
Processing Complete")
1 = Valve is ready for communication (has received the rising edge of "Initial Data
Processing
Complete")
1
ZERO EXECUTED
ZERO successful executed, active for 2 seconds
2
PING PONG RX-BIT
PING PONG RX BIT, is inverted and transmitted back to the fieldbus master (PLC), See
chapter: 3.1.3
Communication and timing control between Master (PLC) and Station
(Valve)
3
PRESSURE SIMULATION
0 = off
1 = on
4
PRESSURE SETPOINT
REACHED
0 = The actual pressure is not within 2% of the pressure setpoint
1 = The actual pressure is within 2% of the pressure setpoint
5-6
NOT USED (reserved)
-
7-8
ACCESS MODE
bit 8
bit 7
0 0
= LOCAL
0 1
= REMOTE
1 0
= LOCKED
9
WARNINGS ACTIVE
0 = No WARNINGS
1 = At least one WARNING of the warning bitmaps is active (GENERAL WARNING bitmap and
EXTENDED WARNING bitmap)
10-15
NOT USED (reserved)
-