Installation, Operating & Maintenance Instructions
Series 615 DN 40 (I.D. 1.5”), RS485
VAT Vakuumventile AG, CH-9469 Haag, Switzerland
Tel +41 81 771 61 61 Fax +41 81 771 48 30 [email protected] www.vatvalve.com
289111EB
2013-02-05
64/96
Setup function
Command
Acknowledgement
(within 10ms after reception of command)
Description
VALVE
CONFIGURATION
Set
[s:04][abcdefgh][CR][LF]
[s:04][CR][LF]
Get
[i:04][CR][LF]
[i:04][abcdefgh][CR][LF]
data length 8 characters
a
valve position after power up:
0
= closed,
1
= open
b
valve position after power failure:
0
= closed,
1
= open
c
0
(reserved, do not change)
d
0
(reserved, do not change)
e
0
(reserved, do not change)
f
0
(reserved, do not change)
g
0
(reserved, do not change)
h
0
(reserved, do not change)
This function does the valve configuration.
SENSOR
CONFIGURATION
Set
[s:01][abcdefgh][CR][LF]
[s:01][CR][LF]
Get
[i:01][CR][LF]
[i:01][abcdefgh][CR][LF]
data length 8 characters
a
0
= no sensor
1
= 1 sensor operation (sensor 1 input)
2
= 2 sensor operation with automatic changeover
(low range = sensor 2 input, high range = sensor 1 input)
3
= 1 sensor operation (sensor 2 input)
4
= 2 sensor operation with automatic changeover
(low range = sensor 1 input, high range = sensor 2 input)
Note:
Sensor operation modes 2, 3 and 4 are possible with 2 sensor hardware
(615 . . - . . .
K
- . . . . only.
Note:
For applications where the high range sensor is used for for monitoring
purpose only, select sensor operation modes 1 or 3 for pressure control with
low range sensor and read high range sensor from «SENSOR 2 READING»
resp. «SENSOR 1 READING».
b
1
= ZERO enabled,
0
= ZERO disabled
cdefgh
High
range / Low range sensor full scale ratio * 1‟000 (
1000
…
100000
).
In case of a 1 sensor valve use any value within the valid range.
This function does the sensor configuration for pressure control.