Installation, Operating & Maintenance Instructions
Series 615 DN 40 (I.D. 1.5”), RS485
VAT Vakuumventile AG, CH-9469 Haag, Switzerland
Tel +41 81 771 61 61 Fax +41 81 771 48 30 [email protected] www.vatvalve.com
289111EB
2013-02-05
47/96
3.11.3 Tuning of pressure control (soft pump)
Normally the default settings will result in good pressure control performance. For some applications tuning may be
required to improve performance.
The tuning procedures for each parameter (grey boxes) and its default values are described separately below. Strictly
keep the procedure order.
No
No
No
P-Gain to
adjustment
Pressure
control
ok ?
Valve speed
adjustment
Start
End
Pressure
control
ok ?
Contact
VAT
Pressure
control
ok ?
P-Gain to calculated
value and valve speed to
maxium