Installation, Operating & Maintenance Instructions
Series 615 DN 40 (I.D. 1.5”), RS485
VAT Vakuumventile AG, CH-9469 Haag, Switzerland
Tel +41 81 771 61 61 Fax +41 81 771 48 30 [email protected] www.vatvalve.com
289111EB
2013-02-05
29/96
3.6.5 Pressure control configuration
Local operation
:
(„Control View‟ or „Control Performance Analyzer‟)
Remote operation
:
4. Open CV or CPA
5. Go to «Tools» > «Terminal» and send setup command s:02 according
to application needs. (possibility of adjustment see below)
Command
Acknowledgement
(within 10ms after reception of
command)
Describtion
Set
s:02abcdefgh
configuring Control mode
a
s:02
s:02a
switch to Control mode
a
without
configuring
s:02
Get
i:02
get configuration actual Control
mode
i:02abcdefgh
i:02a
get configuration Control mode
a
i:02abcdefgh
This command selects control mode, gain factor, sensor response time,
setpoint ramp time, p-gain, i-gain and pump down for the PID controller.
data length 8 characters
a
Control algorithm:
0
= adaptive downstream (default)
1
= fixed PI downstream control
2
= fixed PI upstream control
3
= soft pump
Note:
For adjustment of Control algorithm see table below.
Note:
Refer to chapter: «RS232
Command syntax» > «RS232
co
mmands» > „PID CONTROLLER
CONFIGURATION„.
a (control mode)
parameter description
0
adaptive
downstream
b
Gain Factor: (default is
8
= 1.00)
0
= 0.10,
1
= 0.13,
2
= 0.18,
3
= 0.23,
4
= 0.32,
5
= 0.42,
6
= 0.56,
7
= 0.75,
8
= 1.00,
9
= 1.33,
A
= 1.78,
B
= 2.37,
C
= 3.16,
D
= 4.22,
E
= 5.62,
F
= 7.50,
G
= 0.0001,
H
= 0.0003,
I
=0.001,
J
= 0.003,
K
= 0.01,
L
= 0.02,
M
= 0.05
c
Sensor Response Time (s): (default is
0
= 0.00)
0
= 0.00,
1
= 0.02,
2
= 0.04,
3
= 0.06,
4
= 0.08,
5
= 0.10,
6
= 0.15,
7
= 0.20,
8
= 0.25,
9
= 0.30,
A
= 0.35,
B
= 0.4,
C
= 0.50,
D
= 0.60,
E
= 0.80,
F
= 1.00
d
Setpoint Ramp Time (s): (default is
0
= 0.0)
0
= 0.0,
1
= 0.5,
2
= 1.0,
3
= 1.5,
4
= 2.0,
5
= 2.5,
6
= 3.0,
7
= 3.5,
8
= 4.0,
9
= 4.5,
A
= 5.0,
B
= 5.5,
C
= 6.0,
D
= 6.5,
E
= 7.0,
F
= 7.5,
G
= 8.0,
H
= 8.5,
I
= 9.0,
J
=9.5,
K
= 10.0
e, f, g, h are
not used. Set
0000