91
13.6
Checking the system parameters
The system parameters are checked via the web interface.
•
Select the System page.
No. Description
1
Battery charger overview
2
Batter converter overview
3
Battery module serial number overview
4
Error list / grid and plant error list
5
Battery modules - battery chargers overview
13.6.1
Checking the current sensor values
•
The current sensor values are displayed in the battery transducer overview (2).
•
Check the current sensor values (I network L1, I network L2 and I network L3) to ensure that they are
realistic values.
•
If a current sensor value is approximately 0, even though this phase is currently charged, it may be that
the connection between the current sensor and the energy storage system is faulty.
In this case, if necessary, charge all the phases separately by switching consumers on selectively.
•
If necessary, check the current flow through all three phases with the clamp-on ammeter!