80
12.4.5
Network
•
The network parameters of the frequency-dependent active power adjustment P(f) and the grid and
plant protection must be adapted to the requirements of the respective country.
•
Change the settings - if necessary.
Note:
The change of network-relevant parameters must be approved by the electricity grid operator.
No. Description
1
Country ID
2
Network parameters
3
Idle power parameters
4
Power restriction parameters
12.4.5.1
Idle power compensation
On the factory side, the power factor cos
φ
to compensate for the idle power is set to 0.95. This value may need
to be changed according to the specifications of the respective electricity grid operator. In the
Idle power
function drop-down list, manual entry, entry according to Q(P) characteristic and entry according to Q(U)
characteristic can be chosen from to set the cos
φ
.