11.8
Network connection preparation (black plug)
For the network connection, the 5-wire network connection line must be connected to the
plug connection (black plug) provided
•
Strip the connection line 40mm at the end.
•
The PE conductor must be 5mm longer than the other four conductors (L1, L2, L3, N). Shorten these
conductors accordingly.
•
Strip the five wires of the house connection at the ends 8mm.
•
In the case of fire-wired conductors, wire terminations are to be used.
•
Unscrew the cap nut of the tension relief.
•
Remove the plug housing: To this end, release the catch by pressing the two side detents
simultaneously.
•
Slide the cap nut and the plug housing over the line.
i
A flexible, non-metallic sheathed cable facilitates the mounting work.
No.
Description
1
Cap nut for tension relief
2
Plug housing
3
Opening for latching when inserting
To release: Press in detent
4
Contact insert
5
Opening for detent (two-sided).
For latching when mounting the plug