32
Värmebaronen 400V3~: EP 450, -510, -540, -600, -700 TL / 690V3~: EP 600, -750 TL
Technical Data
The electric boiler is CE marked as a unit and
is classified as pressure equipment according
to Directive 2014/68/EU, Article 4(3).
The electric boiler can be supplied with factory-
fitted safety equipment, reviewed by accredited body
according to EN 12828.Factory-fitted safety equipment
includes:2 x safety valves.2 x high pressure guards.
1 x low pressure guard.1 x automatic vent valve.
With factory-fitted safety equipment, the boiler can be
installed without expansion tank according to EN 12828.
Double circulation pumps and flow guards are not
required. The boiler can cope with zero flow from
a safety perspective.
A steam-collecting vessel is not required. The safety
valves are fitted directly on the boiler's safety pipe.
Final examination, under national laws, that the electric
boiler has the necessary safety equipment shall be
carried out by an accredited body when assessing
the monitoring interval for the electric boiler.