Värmebaronen 400V3~: EP 450, -510, -540, -600, -700 TL / 690V3~: EP 600, -750 TL
Operation and maintenance
Before switching on and first operation the boiler,
all operating conditions must be met, check:
Power cables' connections; tighten them.
That the boiler and heating system are full of water
and vented and that the air vents are open so that they
can let air out.
That all necessary valves are open.
That the circulation pump is working and the flow direction
is correct.
That any safety valves are working.
That no tools or similar have been left behind the
busbar system.
That safety equipment is working as intended.
Start - first operation
Switch on the power
to the boiler, follow the
instructions in the window.
Windows will not appear if
the manual restart function
is bypassed, see "Restart
after power cut".
RESTART AFTER
POWER CUT
PRESS START FOR
OPERATION
If the conditions are
correct, this window will
appear for a short time.
The information varies
slightly depending on the
equipment of the boiler.
VÄRMEBARONEN AB
EPxxx xxxV~ xxxx
vx.xx (AUT)
ENGLISH
>>>>>>>>>><<<<<<<<<<
The Operating Menu is then
displayed. The information
varies slightly with the
boiler's equipment.
SINGLE T outside xx°C
CP� VENT�
ACTUALTEMP XX°C
OUTPUT XXX.X kW
ĮTEMP.SET POINT xx°C
- MENU SELECTOR
If the bottom row switches
between displaying this,
the cause is displayed
when
is held down,
see "Alarm - warning -
information".
- MENU SELECTOR
PRESS OK FOR INFO
When the boiler is first operated, the following param-
eters must be checked/adjusted. More information is
available under 'Menus'. Note the settings in 'Notes'
Installation menu
Load guard
The setting values
are calculated.
ĮCURRENT LIMIT x.xxA
ĮMARGIN x.xxA
Output limiting
Number of power stages
the boiler should work with.
ĮMAX POWER (30)xxx.xkW
External stage limitation
Potential-free blocking,
0-5V, 0-10V or 4-20 mA.
ĮEXT PWR LIMIT NO
External temperature
setpoint
0-5V, 0-10V or 4-20 mA.
ĮEXT SET TEMP NO
Circulation pump
Operating options, NEVER,
AUTO, ALWAYS or ECO
(only with UTK, optional).
ĮCP FUNCTION NEVER
Delayed reconnection
Reconnection after
power cut
ĮDELAY ENABLED
Over temperature
ĮO-TEMP FUNCTION: Rel
ĮO-TEMP LEVEL: +10°C
Adjustment menu
Max and min setpoints
Limits of the range for
setting the boiler's
temperature setpoint.
ĮMAX SET LIMIT 95°C
ĮMIN SET LIMIT 20°C
Setting of heat
curve
Boiler with OTC.
- - î î î î î î - -
Į P1, T o20: 20°C
P2, T o15: 27°C
P3, T o10: 33°C
P4, T outside= +5: 40°C
P5, T outside:= 0: 45°C
P6, T outside 0 -5: 49°C
- - ï ï ï ï ï ï - -
- - î î î î î î - -
Į P7, T outside=-10: 53°C
P8, T outside=-15: 57°C
P9, T outside=-20: 60°C
P10, T outside=-25: 62°C
P11, T outside=-30: 63°C
TEMP. ADJUSTMENT: 0°C
- MENU SELECTOR
Operating menu
Boiler temperature,
setpoint
Standard boiler.
ĮSET TEMP 70°C
Pressure guards
If the boiler was supplied with safety equipment,
see 'Alarm - load-break switches and safety guards',
High-pressure guard and Low-pressure guard.