background image

12

Värmebaronen 400V3~: EP 450, -510, -540, -600, -700 TL / 690V3~: EP 600, -750 TL

Window one

ĮCURRENT LIMIT     x.xxA

 CURRENT MARGIN       x.xxA

 MAX PWR (30)      xxx.xkW

 POWER SPEEDSTEP 

 EXT PWR LIMIT         NO

 EXT SET TEMP           NO

 CP FUNCTION NEVER

  - - ï ï ï ï ï ï - -

Load switch

ĮCURRENT LIMIT     x.xxA
ĮCURRENT MARGIN    x.xxA

Setting values are calculated, for example:
Main fuse: 

800 A

Current transformer:  1000/5
Boiler, EP 510 HT: 17 kW/stage/24.5 A. See “Technical data”.

Current transformer's conversion ratio:

1000

5

200

Current limit

main fuse current transformer's 

conversion ratio

= 800 

A200

4

Margin

size of power stage in ampere current 

transformer's conversion ratio

= 24.5 A  

200

0.12

ĮMAX PWR   (30) 600.0kW

Selection of the power with which the boiler is to operate. 
The figures in brackets show the number of stages.

ĮPOWER SPEEDSTEP

Quick increase/reduction of power in connection with checks 
and acceleration of the delay when it is active. If the delay is 
active, the display shows

ĮSPEEDING TIME BLOCK

Release the button and press it again if you want quick 
increase/decrease.

ĮEXT PWR LIMIT       NO

Stage limit with external signal, 0-100% of selected power,  
“Max. POWER”.
NO: 

internal limit. 

0-5V: 

limit with 0 - 5 V. 

0-10V: 

 limit with 0 - 10 V or potential-free blocking.

4-20mA:  limit with 4 - 20 mA.

ĮEXT SET TEMP         NO

Temperature setpoint via external signal.
NO: internal setpoint.
0-5V: 

nominal value with 0 - 5 V (0-170° C).

0-10V:  nominal value with 0 - 10 V (0-170° C).
4-20mA: setpoint with 4-20 mA (0 - 170°C).

ĮCP FUNCTION   NEVER

Operating method for circulation pump supplied with power 
by the boiler:
NEVER:  no pump operation/pump switched off
AUTO:   The pump starts before power is connected and stops 

one minute after all power has stepped out. If the 
pump is not in operation, it is run once daily. In the 
event of over temperature, the pump starts and is in 
operation until the over temperature situation ends, 
even if all power is disconnected.

ALWAYS:Pump always in operation.

ECO: 

 Only with UTK, option. Pump stop with 
maintenance operation, when the outdoor 
temperature meets the set temperature according 
to 

 ECO, OUTDOOR TEMP +17°C

 in the 

Adjustment menu

Installation menu

Содержание EP 450 TL

Страница 1: ...EPTL450 750_400 690V_fw114_revC_220830 Installation and maintenance 30 stage electric boilers 400V3 EP 450 TL EP 510 TL EP 540 TL EP 600 TL EP 700 TL 690V3 EP 600 TL EP 750 TL...

Страница 2: ...justment Operation and maintenance 17 Alarm warning information 18 Red indicator flashing Alarm Yellow indicator flashing warning Green indicator flashing information Alarm load break switches and saf...

Страница 3: ...mA Max limit C Min limit C UTK heating curve P1 Toutside 20 C C P7 Toutside 10 C C P2 Toutside 15 C C P8 Toutside 15 C C P3 Toutside 10 C C P9 Toutside 20 C C P4 Toutside 5 C C P10 Toutside 25 C C P5...

Страница 4: ...ore service repairs Never carry out maintenance work service on pressure bearing parts when they are pressurised The boiler may not be used by children or people with physical or mental impairments No...

Страница 5: ...arm indication Alarms are indicated on the boiler s control panel Connection for external indication of a buzzer alarm alternating potential free relay output Stainless steel immersion heaters The imm...

Страница 6: ...the other menus Displayed as follows E X I T To OPERATING MENU with To the previous window with To the following window with MENU SELECTOR To MENU SELECTOR with ADJUSTMENT MENU INSTALLATION MENU INFO...

Страница 7: ...UAL PEC 000 PEAK PEC 000 ACTUAL CURRENT 0 00A MENU SELECTOR V RMEBARONEN AB EPxxx TL xxxV xxxx vx xx AUT ENGLISH RESTART AFTER POWER CUT PRESS START FOR OPERATION ENGLISH PEC 1 xxxx CONTRAST 20 BACKLI...

Страница 8: ...t change the content with an UP DOWN arrow Parameters with a large setting range have an acceleration function when the button has been pressed for a while moves the index arrow up between rows of edi...

Страница 9: ...cause is displayed when is held down see Alarm warning information MENU SELECTOR PRESS OK FOR INFO When the boiler is first operated the following param eters must be checked adjusted More information...

Страница 10: ...CTUAL TEMP XX C Information current boiler temperature ACTUAL POWER 000 0kW Information current connected power TEMP SET VALUE 70 C Setting desired boiler temperature 20 95 C setpoint The setting rang...

Страница 11: ...tting to be carried out SHUT DOWN BOILER N Set boiler in standby position switched off Window two P1 T outside 20 20 C P2 T outside 15 27 C P3 T outside 10 33 C P4 T outside 5 40 C P5 T outside 0 45 C...

Страница 12: ...K Release the button and press it again if you want quick increase decrease EXT PWR LIMIT NO Stage limit with external signal 0 100 of selected power Max POWER NO internal limit 0 5V limit with 0 5 V...

Страница 13: ...o function Activated delayed power connection PEC MAX LIMIT 200 Limit value 0 500 quality factor for PEC function alarm O TEMP FUNCTION Rel O TEMP LEVEL 10 C Over temperature function Rel over tempera...

Страница 14: ...last switced on PEAK PCB TEMP xx C The highest temperature of the relay circuit board since the electronics were last switced on ACTUAL PEC xxx PEAK PEC xxx Result of leakage current measurement The...

Страница 15: ...SPECIAL MENU STB TEST E X I T ENGLISH Language selection Available languages Swedish English and German PEC 0 xxxx PEC 1 PEC function active PEC 0 PEC function disabled See HIGH PEC Under Alarm warnin...

Страница 16: ...rned off A point on insulation testing of the immersion heaters should be added to the maintenance plan The break value for the PEC function is adjustable Safety valves To maintain the safety function...

Страница 17: ...is displayed V RMEBARONEN AB EPxxx xxxV xxxx vx xx ENGLISH Press when the arrows on the bottom row point towards the middle so that this window is displayed ENGLISH PEC 1 xxxx CONTRAST 20 BACKLIGHT 1...

Страница 18: ...ircuit or interruption Action Check replace power circuit board R8 TEMP SENSOR PANEL Temperature sensor on panel circuit board Cause Short circuit or interruption Action Check replace panel circuit bo...

Страница 19: ...Yellow indicator flashing warning Automatic reset when the cause has ceased Y1 PEC Cause Increasing PEC values leak current Action See R9 High PEC Y2 OVERTEMPERATURE Cause The boiler temperature is h...

Страница 20: ...TION ACTUAL TEMP 70 C SWITCH TEMP GUARD ARE TRIPPED RESET 1 TEMP GUARD 2 LOAD BREAK ACTUAL TEMP 70 C SWITCH TEMP GUARD H PRESSURE GUARD ARE TRIPPED RESET 1 TEMP GUARD 2 H PRESSURE 3 LOAD BREAK ACTUAL...

Страница 21: ...ff and then to I on The version of the switch is dependent on the boiler model The procedure is not always the same 0 OFF I ON TRIPPED The version of the switch is dependent on the model of boiler The...

Страница 22: ...ssified as good system water When the water is heated some oxygen and carbonic acid are emitted to the expansion tank or vent valves The remainder will react with the metals in the system This corrosi...

Страница 23: ...system without a flash tank 300 kW 105 C The opening pressure of the safety valve is determined by the component in the system that tolerates the lowest pressure Under SS EN 12828 the installation mus...

Страница 24: ...control side of the boiler is supplied with 230V 6 A fused as shown in the figure below The boiler must be preceded by an all pole switch with at least 3 mm breaking distance 1 2 3 4 5 6 7 8 L 10 X01...

Страница 25: ...and secondary current transformers The latter are supplied with the boiler The system adapted primary current transformers xxx 5 A are supplied by the electrician The cable from the primary current tr...

Страница 26: ...r of stages the boiler is permitted to use 1 2 3 0 10 Vdc GND 36 0 10 V output signal of boiler temperature 0 10 V is equivalent to 0 170 C 1 2 3 GND 0 10 Vdc 36 Outdoor temperature sensor boiler with...

Страница 27: ...installation 27 V rmebaronen 400V3 EP 450 510 540 600 700 TL 690V3 EP 600 750 TL...

Страница 28: ...oad 230 V 2 A 27 Potential free relay output for cooling fan Max load 230 V 2 A A fan is included in EP 450 510 and 700 TL optional for other models 28 Potential free relay output for buzzer alarm 29...

Страница 29: ...1 2 1 2 N N 19 1 13 1 6 1 PANEL K7 K6 1 4 2 J23 J17 J16 J22 J24 J15 J11 J12 J13 J14 J4 J8 J3 J10 J6 J2 J1 J9 J5 J7 J18 J19 J20 N1N2 N2 K2 K1 K4 K3 N1 K5 K9 K8 N X03 1 4 2 8 30 M 1 2 3 4 5 6 7 8 L 10 N...

Страница 30: ...K4 14 K5 15 K6 16 K7 17 K8 18 EP450TL Immer sion heater 2 15 kW 5 7 2 15 kW 10 11 13 3 20 kW K4 17 22 25 K5 18 23 28 6 20 kW K6 8 9 12K7 14 20 24 K8 27 26 29 19 3 23 3 kW 3 23 3kW 15 kW 3 23 3 kW Outp...

Страница 31: ...7 10 11 13 16 K4 17 22 25 27 K5 18 23 28 30 K6 1 3 4 6 K7 8 9 12 15 K8 14 20 21 24 K9 19 26 29 EP 540 TL 18 kW 18 kW 36 kW 2 18 kW 72 kW 4 18 kW 144 kW 8 18 kW 270 kW 15 18 kW EP 600 TL 20 kW 20 kW 4...

Страница 32: ...ressure guards 1 x low pressure guard 1 x automatic vent valve With factory fitted safety equipment the boiler can be installed without expansion tank according to EN 12828 Double circulation pumps an...

Страница 33: ...6 16 7 20 9 A Cable flange 2 x FL 33 2 x 60 mm Cable connection 4 x 95 240 Al Cu Up to 240 mm2 round pressed cable can be connected Volume 315 litre Calculation pressure 0 66 MPabar Test pressure 0 8...

Страница 34: ...ard two 49 Low pressure guard 62 Cable flanges 63 Adjustable foot bolts 64 Automatic vent valve 65 Safety pipes 66 Flow connection 67 Return connection 68 Drain valve 69 Safety valves 2 Included in fa...

Страница 35: ...included in EP 450 510 and 700 TL otherwise optional 42 Current transformer PEC function 50 Connection 230V operating voltage fuse 6 A 51 Blade fuse holder F1 fuse power group one 52 Blade fuse holder...

Страница 36: ...5 36 8 3 9 75 8 2 2 3 40 30 3 8 80 6 9 2 0 Outside temperature sensor option C k V C k V 30 47 4 3 5 6 8 2 4 25 34 7 4 1 10 5 4 2 1 20 25 9 3 9 15 4 2 1 8 15 19 5 3 6 20 3 4 1 6 10 14 8 3 3 25 2 7 1 3...

Страница 37: ...0V 30 110038 20 kW 400V 9 1 30 110039 23 3 kW 400V 9 14 30 110091 20 kW 690V 30 119155 25 kW 690V 30 Load break switch 130067 2 2 2 130068 2 2 2 2 Contactor 170080 K6 K8 K3 K8 K3 K8 K3 K8 K3 K9 170081...

Страница 38: ...return valve for air vent Air vent High pressure guard Low pressure guard 1 1 1 1 Safety equipment closed systemContents in addition to some of the below specified safety valves 245076 245078 440196 4...

Страница 39: ...general information 39 V rmebaronen 400V3 EP 450 510 540 600 700 TL 690V3 EP 600 750 TL...

Страница 40: ...V rmebaronen AB Arkelstorpsv gen 88 SE 291 94 Kristianstad Tel 46 44 22 63 20 www varmebaronen se www varmebaronen com info varmebaronen se...

Отзывы: