CPS-2C USER’S GUIDE
CPS-2C Section
C-27
LO
REC
LO
REC
High Alarm 2
Hi AL
This parameter is used to establish the relative temperature/static pressure
at which a high alarm condition will occur. When
Probe Readout 2
is above
the
Main Set Point
+
High Alarm 2
, a high alarm condition will occur. This
parameter is adjusted in 0.1° increments from 0.5°F to 40.0°F (0.3°C to
22.2°C) or from 0.000’’H
2
O to 0.500’’H
2
O in 0.001’’H
2
O increments.
Probe 2 Min (POS 6)
Probe 2 Minimum
This parameter displays the lowest value reached by
Probe 2
since the
CPS-2C was powered up or since this parameter was last cleared. To reset
this value to the actual
Probe 2 Readout
, press the SET/CLR button. The
Probe 2 Minimum
is displayed to the nearest 0.1° from -58.0°F to 140.0°F
(-50.0°C to 60.0°C) or from -0.500’’H
2
O to 0.500’’H
2
O to the nearest
0.001’’H
2
O.
Low Alarm 2
Lo AL
This parameter is used to establish the relative temperature/static pressure
at which a low alarm condition will occur. When
Probe Readout 2
is below
the
Main Set Point
+
Low Alarm 2
, a low alarm condition will occur. This
parameter is adjusted in 0.1° increments from -40.0°F to -0.5°F (-22.2°C to
-0.3°C) or from -0.500’’H
2
O to 0.000’’H
2
O in 0.001’’H
2
O increments.
Probe 1 Min (POS 7)
Probe 1 Minimum
This parameter displays the lowest value reached by
Probe 1
since the
CPS-2C was powered up or since this parameter was last cleared. To reset
this value to the actual
Probe 1 Readout
, press the SET/CLR button. The
Probe 1 Minimum
is displayed to the nearest 0.1° from -58.0°F to 140.0°F
(-50.0°C to 60.0°C) or from -0.500’’H
2
O to 0.500’’H
2
O to the nearest
0.001’’H
2
O to the nearest 0.001’’H
2
O.
Low Alarm 1
Lo AL
This parameter is used to establish the relative temperature/static pressure
at which a low alarm condition will occur. When
Probe Readout 1
is below
the
Main Set Point
+
Low Alarm 1
, a low alarm condition will occur. This
parameter is adjusted in 0.1° increments from -40.0°F to -0.5°F (-22.2°C to
-0.3°C) or from -0.500’’H
2
O to 0.000’’H
2
O in 0.001’’H
2
O increments.
Alarm Code
A.CODE
This setting displays the alarm condition. This parameter displays 0 when
no errors have been detected. This indicates that the controller is operating
properly. The alarm LED (
) on the faceplate will be lit up if an alarm
code is actually displayed. The alarm code refers to the following table.
Содержание CPS-2C
Страница 3: ...CPS 2C WIRING DIAGRAM CPS 2C Section A 3 WIRING DIAGRAM CPS 2C SECTION A ...
Страница 7: ...CPS 2C INSTALLATION CPS 2C Section B 7 INSTALLATION CPS 2C SECTION B ...
Страница 20: ...CPS 2C USER S GUIDE Section C 20 CPS 2C USER S GUIDE CPS 2C SECTION C ...
Страница 38: ...CPS 2C INDEX WARRANTY INDEX WARRANTY CPS 2C SECTION D ...
Страница 42: ...CPS 2C VER 1 2 November 21 2011 ...