CPS-2C INSTALLATION
Section B-18
CPS-2C
Specifications
Storage temperature
-4°F to 131°F (-20°C to 55°C)
Operating temperature
32°F to 113°F (0°C to 45°C)
Humidity
90% maximum Non-condensing
Weight
2.4 lb (1.1 kg)
Size
8 1/2” x 7” x 4 3/4” (22.6 cm x 17.7 cm x 11.5
cm)
Protection index
IP 66
Warranty
2 years
POWER SUPPLY
Operational voltage range (SW1 @ 115V)
92 to 125VAC
Operational voltage range (SW1 @ 230V)
184 to 250VAC
Operational frequency range
45 to 65 Hz
Power supply circuit consumption (CPU
Board)
6 VA
SOURCE 8 VAC
Voltage range
6.5 to 13VAC
Maximum current allowed
50mA
PROBE INPUTS
Temperature probe
2004-10K
Static Pressure probe
GE-SP1
Maximum wire length
500 feet (150 m)
Recommended wires
2 conductors, stranded, shielded, AWG #22
ALARM RELAY
Maximum current
1 A at 30VDC
Delay before activation
Between 6 and 8 seconds
OUTPUT RELAYS
Maximum Current
1HP @ 240VAC, 1/2HP @ 120VAC,
10A@240VAC
Caution Notice
These relays are rated by UL and CSA at 1HP
@ 240VAC, 1/2HP @ 120VAC. However, for
outputs requiring frequent activation (ex: inlet
working on a timer) it is recommended not to
use more than 1/2HP @ 240VAC, 1/4HP @
120VAC per relay.
Important Notice:
-
It is important to have a backup system in case of a system failure.
-
Low-voltage and high-voltage wire must be passed through different
conducts at least 1 foot (30 cm) apart. If low-voltage and high-voltage
conduits must be crossed, the crossing must be at a 90-degree angle.
- All wiring must be made by a certified electrician and conform to local
electrical regulations.
Содержание CPS-2C
Страница 3: ...CPS 2C WIRING DIAGRAM CPS 2C Section A 3 WIRING DIAGRAM CPS 2C SECTION A ...
Страница 7: ...CPS 2C INSTALLATION CPS 2C Section B 7 INSTALLATION CPS 2C SECTION B ...
Страница 20: ...CPS 2C USER S GUIDE Section C 20 CPS 2C USER S GUIDE CPS 2C SECTION C ...
Страница 38: ...CPS 2C INDEX WARRANTY INDEX WARRANTY CPS 2C SECTION D ...
Страница 42: ...CPS 2C VER 1 2 November 21 2011 ...