Vaporless ISM-4080 Скачать руководство пользователя страница 14

14 

 

6.

 

System Purge

  

Authorize the dispenser. The pump should start running. On the right-hand pressure gauge of the LDT-
890, watch for the pump to achieve operating pressure. 

 
7.

 Check all connections for leaks. Correct any fault conditions. 

 

8.

   With the large beaker (1000 ml) under the LDT-890 discharge port, set the selector to the DISPENSER 

NOZZLE position. Purge the tester of air by allowing 800 to 1000 ml of fuel to flow into the beaker. 
Continue  until  air  spitting  has  stopped.  After  purging  the  LDT-890,  set  the  selector  back  to  the 
PRESSURE STEP TEST position.  

 

9. Bleed-Back Measurement  

Remove the dispenser authorization. The pump should stop running. Unless there are fault conditions 
such as a leak or significant thermal contraction, the line pressure should stabilize at 20 – 30 PSI for 
fractional horsepower pumps, or 20 – 50 PSI for higher pressure pumps.  
 

10. 

With  the  large  beaker  under  the  LDT-890’s  discharge  port,  carefully  move  the  selector 

counterclockwise until fuel begins to flow. Monitor the line pressure and when it falls to 14 PSI rapidly 
return the selector to the PRESSURE STEP TEST position. For a more precise measurement, have 
one tech monitor ISM display while another tech drains line pressure, when the display changes from 
MONITOR to DELAY, stop flow. 

 

11.

 With the flow of fuel stopped, empty the collection beaker.  

 

12.

 With the small (250 ml) beaker under the LDT-890 discharge port, carefully move the selector to the 

DISPENSER NOZZLE position. Fuel will begin to flow into the beaker. When fuel stops flowing, 
return the selector to the PRESSURE STEP TEST position. 

 

13.

 Note the volume of fuel collected. This volume is referred to as bleed-back. Repeat the collection 

process several times to confirm the bleed-back volume.  

Note:

  Depending  upon  the  measured  volume,  the  use  of  the  large  beaker  may  be  needed.  When 

possible,  the  small  beaker  provides  more  accurate  measurements.  The 

averaging  of  several 

consecutive samples

 is necessary to accurately determine the bleed-back volume.  Enter resiliency 

value into ISM-4080 controller (see page 10).  

 
This completes the bleed-back measurement procedure and set-up of the ISM repressure cycle. To ensure 
proper installation and system calibration, a 3 GPH leak test must be performed.  

 
LEAK DETECTOR TEST AT 3 GPH  

 
Whether the ISM is fitted to a new installation or retrofit to an existing site, a test of the leak detector must 
be  performed. This  is  done  to  ensure  that  the VMI  Leak  Detector  is  operating  normally  and  that  the 
selected ISM delay time is long enough for the VMI Leak Detector to return to its reset position.  
 
The following statements outline a procedure for testing the operation of the VMI Leak Detector. This 
procedure assumes the use of the Vaporless Model LDT-890 Leak Detector Tester to perform this task.  

Содержание ISM-4080

Страница 1: ...1 Quality Petroleum Equipment Solutions for Over 30 Years ISM 4080 Electro Mechanical Line Leak Detection Installation Operation Manual Rev 11 11 2020...

Страница 2: ...es 3GPH line leak detection To alleviate this issue the ISM 4080 will authorize one pump first allow one leak detector to search for a line leak and then after the line has been cleared passed start t...

Страница 3: ...gn characteristics that minimize the effects of poor main grounds and transient noise However good design may not overcome all of the problems of a poorly grounded site or a site with a high amount of...

Страница 4: ...become the tank monitor s authorizations In this manner the pump starting and stopping is subject to the site sensors Alternatively Sump Alarms and E stop can be wired to break main power to the ISM...

Страница 5: ...am found on page 22 connect the IS wiring in the junction box using the supplied wire nuts and di electric grease Use the wiring instructions found on page 22 for the connection to the ISM 4080 contro...

Страница 6: ...s run in response to low pressure completes with a pass An Alarm is initiated at a failure to pressurize the line mechanical electronic problem or due to a 3 GPH line leak FRONT PANEL The ISM 4080 Con...

Страница 7: ...iscussed below TEST Test button not active on the ISM 4080 system PRINT Print button not active on the ISM 4080 system RESET This button is VERY IMPORTANT WILL RESET ALARMS RESTART PUMP S o EXAMPLE If...

Страница 8: ...next If the unit is configured the boot screen will display for about 10 seconds and then move to the Home Screen The home screen will look something like this P 1 T 1L PRES HI MONITOR AL N This scre...

Страница 9: ...system Push ENTER NUM SUCTION CV 0 is the default only used for commercial suction PRODUCT 1 0 pumps Push ENTER NUM PRESSURE CV 0 is the default If controlling transition valves PRODUCT 1 0 enter app...

Страница 10: ...change the values displayed below unless you have consulted with VMI Push ENTER REPRESS TIME MIN Use the UP and DOWN ARROWS to adjust the PRODUCT 1 __ _ value between 0 and 20 minutes Push ENTER DELAY...

Страница 11: ...to adjust the number of repressurization attempts before alarm output Factory default is 1 Push ENTER ALARM ACTION CONFIGURED AT THE FACTORY DO NOT MODIFY Push MENU SET DATE TIME Push ENTER SET DATE U...

Страница 12: ...DETAILS If your site has optional sump sensors integrated into the ISM 4080 System When the presence of liquid is detected by the sump sensor the system will not allow the turbine to operate in the s...

Страница 13: ...ocedure must be repeated for each product CAUTION Eye protection required during the calibration and testing process 1 Disable ISM Repressure Cycle With power applied to the ISM disable repressurizati...

Страница 14: ...of fuel stopped empty the collection beaker 12 With the small 250 ml beaker under the LDT 890 discharge port carefully move the selector to the DISPENSER NOZZLE position Fuel will begin to flow into t...

Страница 15: ...eled CALIBRATE PRESSURE Adjust the pressure on the left hand pressure gauge to 10 psi 5 Using the small beaker 250 ml collect a sample of fuel over a 30 second interval If the volume is not 95 ml on t...

Страница 16: ...the dispenser authorized the pump will start running Again note that with the selector in the GPH TEST position a 3 gph leak has been introduced to the system Watch the right hand pressure gauge as t...

Страница 17: ...rted 16 At the end of the delay timing cycle the ISM will automatically turn on the pump Pressure will begin to build but will stop at the value observed in Step 10 indicating that the leak detector h...

Страница 18: ...Turbine Output 4 Control Valve Outputs BROWN Control Valve Output 1 RED Control Valve Output 2 Alarm Outputs YELLOW Alarm Output 1 ORANGE Alarm Output 2 IS SWITCH I O TERMINALS IS switch wiring connec...

Страница 19: ...19...

Страница 20: ...Sump Alarm Output 1 RED Alarm Sump Alarm Output 2 ORANGE Alarm Sump Alarm Output 3 YELLOW Alarm Sump Alarm Output 4 IS SWITCH I O TERMINALS IS switch wiring connections are to be made using low capaci...

Страница 21: ...21...

Страница 22: ...22 Piston Switch Wiring Detail Without Sump Sensor...

Страница 23: ...mp Sensor The Piston Switch may share the wire pair from single point sump sensor with a 100k resistor such as Veeder Root p n VR794380 208 If the MLLD Piston Switch es are to be installed in series w...

Страница 24: ...ufactured by Vaporless Manufacturing Inc Electronics Division 8700 East Long Mesa Drive Prescott Valley Arizona 86314 Phone 928 775 5191 Website www vaporless com Technical Support electronics vaporle...

Отзывы: