INSTALLATION AND MAINTENANCE
Mounting the Thermostat
Install the thermostat at 5 feet (1.5m) above the floor in an area with good air circulation at average
temperature. Avoid locations with drafts or dead spots behind doors, hot or cold air ducts, sunlight
or radiant heat from appliances, concealed pipes or chimneys and unconditioned areas such as
outside walls behind the thermostat.
The wallplate anchors should be spaced 3.5 inches (90 mm) apart in a vertical direction. Pull wires
through the backplate and connect to the appropriate terminals as defined in the Wiring
Configuration.
Mounting the Remote Sensors
Remote indoor sensors (available from your Vantage Dealer) should be installed in locations similar
to those noted in the directions for Mounting the Thermostat above. The thermostat will
automatically detect the presence of a remote sensor.
A remote indoor sensor automatically
overrides the thermostat’s own temperature sensor.
Connect 1 indoor sensor allows the
thermostat to be placed in a utility room. For temperature averaging connect 4 or 9 indoor sensors
(see pages 38 and 39).
Outdoor sensors should be mounted in shaded locations, out of direct sunlight. The thermostat will
automatically detect an external sensor and display its readings. It is possible to connect 1 outdoor
sensor and 1, 4 or 9 external indoor sensors at the same time.
Cleaning the Thermostat
The thermostat can be cleaned with a soft cloth lightly dampened with isopropyl alcohol.