background image

  

 

Page 

29 

MODE.

 To finish configuring, highlight the thermostat station on the list of stations and touch the 

Select

 button on the thermostat. This will display the word CONFIGURE in the lower right side of 

the thermostat LCD. Touch the 

Right Tab

 button under the word CONFIGURE and wait one or two 

seconds for the station to configure. The station may also be configured by typing the serial number 
in the project file; using this method the station will automatically be configured when the system is 
programmed. Once configured the diagnostic LED on the Q ETS3 will blink evenly. 
 
 

Configuration, STHERR101, RadioLink® 

RadioLink stations need to be configured to associate which physical station goes with the station 
in the project file. When the station is initially powered-up, the Status LED will blink three times 
followed by a pause - this means the station is powered correctly but not yet on the network. Before 
uploading the file to the Vantage system, do the following: In Design Center, highlight the 
Thermostat Station. In the Object Editor, click on the Serial Number area and 

type the Serial 

Number in manually

. In QLink, from the menu bar select System | Configure Stations. A list of all 

stations will be displayed on the screen. Highlight the correct station and 

type the Serial Number 

in manually

. Once the Vantage system is programmed and the stations have logged on to the 

RadioLink Controller, the diagnostic LED will blink evenly. 

 
Status LED Diagnostic Information for Q-ETS3 or STHERR101 

During setup and configuration the Q-ETS3 or STHERR101 LED will blink at different intervals. The 
STATUS LED blinks evenly or flashes 2, 3, 4, 5 or 6 times followed by a pause to indicate status 
information. 

 
One Even blink:

 The Q-ETS3 or STHERR101 is correctly configured. 

 

Two blinks:

 Q-ETS3 or STHERR101 is operating correctly but is not configured. 

Содержание STAT

Страница 1: ...Vantage Communicating Thermostat AW000084 D...

Страница 2: ...ols thermostat It has been designed for easy programming to save energy costs and allow a comfortable living environment Features Single Auto Mode programming of yearly Heating and Cooling needs Easy...

Страница 3: ...SETPOINT 8 TEMPERATURE HOLD 9 HEATING AND COOLING MODES 10 FAN MODES 11 TEMPERATURE SETTINGS 12 USER OPTIONS 13 LANGUAGES 13 CHANGE FILTER REMINDER 13 TEMPERATURE UNITS AND CALIBRATION 14 SERVICE INF...

Страница 4: ...22 CONVENTIONAL SYSTEMS 22 HEAT PUMP SYSTEMS 23 CONTROL OPTIONS 23 RESET 24 CONVENTIONAL SYSTEM TEST 25 HEAT PUMP SYSTEM TEST 26 Q ETS3 STHERR101 SETUP AND CONFIGURATION 27 VANTAGE THERMOSTAT INTEGRAT...

Страница 5: ...GHT TAB buttons appears on the bottom of the display screen To SCROLL through the menus and options lightly touch your finger on the outside of the wheel SCROLL to make changes and touch the SELECT bu...

Страница 6: ...fan are animated when the equipment is running HELP button The thermostat s HELP button gives you a quick reminder of how to navigate through the individual menu screens It is intended to provide info...

Страница 7: ...a You can change the time clock readout to display in a 24h or 12h clock For standalone applications the current date and time should be set at initial installation Touch the Left Tab button on the ho...

Страница 8: ...Setpoint Follow these steps to change the thermostat from OCCUPIED to UNOCCUPIED setpoints Choose SETPOINTS from the Main Menu SCROLL to the OCCUPIED or UNOCCUPIED setpoint Touch the LEFT TAB to SET A...

Страница 9: ...hold the TARGET temperature permanently and display HOLD If the user password is required and a valid password has not been entered you can only set a one hour timed hold The thermostat will hold the...

Страница 10: ...ELECT to engage the operating mode AUTO The thermostat automatically selects heating or cooling depending on the indoor temperature HEAT The thermostat controls only the heating system COOL The thermo...

Страница 11: ...SCROLL through the operating modes to get to the fan modes then press SELECT to engage the desired fan mode AUTO The fan runs only when the heating cooling or emergency systems are on For conventional...

Страница 12: ...will engage the HEAT mode heating your dwelling up to 70 F through the winter In the spring the temperature will rise again and the thermostat will change back to COOL mode The SETPOINT s HEAT and CO...

Страница 13: ...save Change Filter Reminder A CHANGE FILTER reminder may be set in the USER OPTIONS menu It can be set from 0 to 12 months Setting it to 0 months disables the CHANGE FILTER reminder After the CHANGE...

Страница 14: ...F If you measure the temperature yourself and believe this thermostat s displayed temperature is off slightly then you can easily adjust the thermostat using these steps SELECT the TEMPERATURE from t...

Страница 15: ...er touching SAVE CHANGES scroll to the next line if you need to enter additional information then follow the procedure just described Power Outages In the event of a power failure the thermostat will...

Страница 16: ...nsors available from your Vantage Dealer should be installed in locations similar to those noted in the directions for Mounting the Thermostat above The thermostat will automatically detect the presen...

Страница 17: ...17 8 X2 C ommunication 2 nd S tage C ooling Y 2 18 9 NC No C onnection 2 nd S tage Heat W2 19 10 X1 C ommunication 20 1 11 2 C C ommon 12 3 FAULT Heat P ump F ault 13 4 FILTE R F ilter P ower 24VAC R...

Страница 18: ...ver possible Vantage Controls recommends wiring the thermostat to the HVAC equipment with a dedicated wire for each connection Where no ground common wire has been included a new ground wire can be pu...

Страница 19: ...and then multiplex one of the outputs W Y G etc onto that ground wire Note that the figure below shows the W terminal being multiplexed but any one of the outputs could be multiplexed The Auxiliary S...

Страница 20: ...on the thermostat to the closest available household ground This will work in most cases because the common of the transformer in the HVAC equipment is also typically tied to household ground If the...

Страница 21: ...use the blank letter to set the password to a blank You can also force the password to time out upon exiting When the USER password setting is ON default is OFF a valid user password is required other...

Страница 22: ...efined as ON in HEAT or ON in COOL The Reversing Valve is default to On in Cool Equipment Settings Conventional Systems You must enter an Installer Password to access the EQUIPMENT SETTINGS from the M...

Страница 23: ...same time Control Options You must enter an Installer Password to access the CONTROL menu from the Main Menu The following settings can be changed DEFAULT OPTION CHANGE HYSTERESIS 2o F 1o C 0 6o F 0...

Страница 24: ...S OCCUPIED 70 F 78 F LANGUAGE ENGLISH USER OPTIONS CHANGE FILTER REMINDER 0 MONTH S TEMPERATURE UNITS IMPERIAL F USER INSTALLER PASSWORD PRESET 1234 OFF INST MAX MIN HEAT 88 F 41 F SETPOINT RANGE COOL...

Страница 25: ...stage cooling should engage 2 nd stage cooling Remain in COOL mode Return to Override menu and SELECT ENGAGE again Second stage cooling should engage 1 st stage heating Change mode to HEAT and overrid...

Страница 26: ...unction and SELECT ENGAGE HOLD again Second stage cooling should engage 1 ST stage heating Mode HEAT Override the setpoint by at least 5 o F 3 o C above room temperature and SELECT ENGAGE HOLD First s...

Страница 27: ...HERR101 RadioLink The thermostat will also work with newer versions of the Q ETS3 or STHERR101 when they become available part numbers may change System Requirements Each Vantage thermostat requires o...

Страница 28: ...system Mounting the Q ETS3 or STHERR101 The Q ETS3 or STHERR101 may be mounted behind the thermostat in a single gang box or may hang through a 1 4 44cm hole in the wall The Black wire X1 and Green w...

Страница 29: ...ed by a pause this means the station is powered correctly but not yet on the network Before uploading the file to the Vantage system do the following In Design Center highlight the Thermostat Station...

Страница 30: ...ation bus the Controller is not in place or is not powered The STHERR101 is not powered Thermostat Setup with InFusion In Area View select the floor and room for the thermostat Click on Vantage Object...

Страница 31: ...Page 31 Wiring to Q ETS3 or STHERR101...

Страница 32: ...Read and or display indoor outdoor temperatures In summation any operation of the HVAC system that can be done directly manually by the client Vantage can do automatically or remotely Disclaimer Vanta...

Страница 33: ...and remove the old Base d Install the new Base and Connect all the old wires to the new Base following the table on page 17 of this manual i e W1 on old thermostat goes to W1 on new thermostat etc e I...

Страница 34: ...xternal indoor sensors must be wired in series parallel configurations with the new thermostat See pages 38 39 for wiring diagrams 5 How to connect Vantage s new Thermostat to a Q ETS that only has tw...

Страница 35: ...The two remote sensors share the RS GND common screw 6 on the new base The 24V and the R terminals on the old thermostat are synonymous with the R terminal screw number 14 on the new thermostat as ill...

Страница 36: ...Page 36...

Страница 37: ...Page 37...

Страница 38: ...Page 38 Temperature Averaging Connecting Multiple Thermostat Sensors for Temperature Averaging Only 4 or 9 sensor configurations are allowed...

Страница 39: ...Page 39...

Страница 40: ...This value is with 24 VAC input voltage and backlight OFF Power Draw Maximum 36 40 mA rms This value is with 18 VAC input voltage and backlight ON Rated Output Current 0 001 A to 1 A continuous per ou...

Страница 41: ...This equipment if installed in strict accordance with the manufacturer s instructions complies with the requirements of IEC 60730 1 This equipment is RoHS compliant Contact Information Vantage Control...