Electrical connections

The unit has a plug connection. The connection box of the unit is located loosely upon the 

unit and can be moved to another place as desired.

Duct connections of unit 

The unit is equipped with two Ø125-mm collars. Necessary connecting pieces (such as 

inner or bent connector) can be attached to the collar. NOTE! The connecting head of the 

connecting piece must not be inserted into the collar by more than 30 mm. Fix the ducts 

steadily and tightly to the relevant outlets. (Note! Unit models L/R). Implement duct insulation 

if needed as defined in the ventilation plan.

Air flow measurement outlets

The fixed air flow measurement outlets of the unit are located in the door below the latch. 

You can measure the total pressure of the supply and extract air ductwork at the measurement 

outlets, using a differential pressure instrument. Pressure readings and air volume tables show 

volume flow rates at various adjustment positions. The red measurement hoses are intended 

for measuring the supply air ductwork and the black measurement hoses for measuring the 

extract air ductwork.

Condensing water connections

The delivery includes a Silent Kick water seal. By connecting a pipe to the water seal the 

water condensing from extract air can be led to a floor drain (not directly to the drain). Silent 

Klick water seal prevents the sound caused by water as the water seal dries up. The pipe 

must not rise after the water seal. The condensation water discharge outlet is located at the 

rear edge in the middle of the unit. Because of this the unit has to be mounted horizontally 

level.

Mounting

VALLOX 121 SE is mounted on the 

wall with a mounting plate as shown 

in the adjacent figure.

Wall mounting

VALLOX 121 SE is mounted in a 

place where temperature does 

not go below +10 °C. Without 

protective enclosure, the unit must be 

located in a place with no acoustic 

disturbance, such as storerooms or 

technical rooms.
VALLOX 121 SE can also be located 

in a damp room, but not in a 

bathroom next to a sauna bath.

Wall construction

The weight of the unit (60 kg) has 

to be taken into account when 

mounting the wall bracket on the wall 

structure. Avoid mounting the unit 

on a hollow, echoing dividing wall 

and on a bedroom wall because of 

sound conduction, or prevent sound 

conduction.

162

12

21

20 60

20 30 30

20

60

11

20

30

30

11

84

84

35 30

35

ø7 14

550

30

25

25

30

°

Wall mounting plate

During mounting, the unit rises 10 

mm higher than the final height.

Bottom edge of  

wall bracket

Room required by  

VALLOX Silent Klick  

water seal.

Bottom edge  

of wall bracket

pcs

Wall mounting plate

Содержание VALLOX 121 SE L

Страница 1: ...de A3560 Models VALLOX 121 SE R VALLOX 121 SE L Electrical connection 230 V 50 Hz 5 7 A Degree of protection provided by enclosures IP 34 Fans direct current Extract air 0 117 kW 0 9 A 106 dm3 s 100 P...

Страница 2: ...ing to the highest measuring result 1 5 carbon dioxide sensors can be connected as options to the VALLOX 121 SE unit The adjustment is switched on off and if needed the setpoint 500 2000 ppm is set at...

Страница 3: ...ples of such situations are high humidity loads such as a swimming pool or a situation where the exhaust air duct has frozen through Remember Switch post heating off when it starts to get too warm in...

Страница 4: ...u To settings menu see manual In order to move to the Settings menu press the and buttons simultaneous ly In the Settings menu you can chan ge setpoints for the ventilation unit 2 3 Week clock control...

Страница 5: ...tory settings can be restored by pressing the and buttons simultaneously Remember to ensure that the setpoints are in accordance with the factory settings for this unit 3 16 Choosing cascade adjustmen...

Страница 6: ...n speed 2 Sp 2 supply air temperature 17 C Temp 17 Move the cursor to the following hour Monday D 1 16 00 H 16 fan speed 4 Sp 4 supply air temperature 20 C Temp 20 Move the cursor to the following hou...

Страница 7: ...by pulling carefully Place a thin sheet board or paper under the fan in order to prevent the bottom tank from being scratched when removing the fan Unfasten the fixing screw of the fan H hex socket he...

Страница 8: ...es at speed 1 check the fan speed Wiring fault in the carbon dioxide sensor in the control panel or in the humidity sensor or the cable is of the wrong type Contact a maintenance company The connectio...

Страница 9: ...ed operating range Volume flow rate Sound power level in supply air duct one duct by octave band LW dB Sound power level in extract air duct one duct by octave band LW dB ADJUSTMENT POSITION AIR FLOW...

Страница 10: ...R2 Post heating radiator M Damper motor 24 VAC Wire colours s blue m black r brown va white vi green p red h grey kv yellow green 16 V 0 V 0 V 230 V 7023500 2011 11 17 JK M1 GND A B PWM1 PWM2 S RH2 S...

Страница 11: ...ke sure that its address is 1 If control panels have the same address they go to bus fault state In this case remove one of the control panels and change the address of the other panel The above menti...

Страница 12: ...water connections The delivery includes a Silent Kick water seal By connecting a pipe to the water seal the water condensing from extract air can be led to a floor drain not directly to the drain Sil...

Отзывы: