5
© VALLOX • We reserve the right to make changes without prior notice.
What the units include can vary depending on the sales area.
Vallox
121
SE
OPERATING INSTRUCTIONS FOR CONTROL PANEL
3.3
Choosing language version
Kieli / Language
English
The desired language is chosen with
the + and – buttons.
3.4
Adjusting time
Adjust time
Press + and -
You can adjust time by simultaneously
pressing the + and – buttons. See se-
parate instructions in 4.2.
3.5
Week programme programming
Adjust wk. prog.
Press + and -
To go to the week-clock programme
programming mode press the + and –
buttons simultaneously. See the instruc-
tions in 4.1.
3.6
Erasing week programme
Erase wk. prog.
Press + and -
You can totally erase the week pro-
gramme by pressing the + and – but-
tons simultaneously.
3.7
Choosing basic humidity level
Rh-level setting
automatic
The basic humidity level can be cho-
sen as either automatic or manual.
The selection is done with the + and
– buttons.
3.8
Basic humidity level setpoint
Basic %RH level
40%
The desired setpoint is chosen with the
+ and – buttons when manual adjust-
ment has been selected as the Rh level
setting (humidity setting, Section 3.7).
3.9 Changing setpoint for carbon dioxide adjustment
CO2 setting
0900 PPM
The setpoint for CO
2
adjustment is cho-
sen with the + and – buttons.
3.10
Adjustment interval
Adjust interval
10
The adjustment interval for humidity and
carbon dioxide adjustments is selected
with the + and – buttons. The adjust-
ment interval refers to minutes.
3.11
Changing operating temperature of
heat recovery cell bypass
Cell bypass
10C
The desired cell bypass temperature
is selected with the + and – buttons. If
outdoor temperature is lower than cell
bypass temperature, the summer/win-
ter damper is in the winter position.
3.12
Mode of operation of fireplace/booster switch
Switch type
fireplace switch
The mode of operation of the switch
(either fireplace or booster switch) is
selected with the + and – buttons.
3.13
Address of control panel
Panel address
1
The address of the control panel is
changed with the + and – buttons. Two
control panels cannot have the same
address. If control panels have the
same address, they go to bus fault state
and do not work.
3.14
Contrast of control panel display
Display contrast
05
The contrast setting for the control panel
display is changed with the + and –
buttons.
3.15
Restoring factory settings
Factory settings
see manual
The general factory settings can be
restored by pressing the + and – buttons
simultaneously. Remember to ensure that
the setpoints are in accordance with the
factory settings for this unit.
3.16
Choosing cascade adjustment for supply air temperature
Cascade adjust
off
Cascade adjustment is chosen to be on
or off with the + and – buttons.
3.17
Choosing post-heating for the unit
Radiator type
Electric rad.
A water or electric radiator is selected
with the + and – buttons, depending on
the type of post-heating radiator the unit
is equipped with.
Note! Choosing the wrong type of
post-heating may cause a faulty post-
heating function.
3.18
Choosing additional heater for unit
Extraheater type
MLV radiator
An electric or MLV radiator is chosen
according to ventilation unit type with
the + and – buttons.
3.19
MLV additional heater setpoint
MLV winter temp
0C
Changing MLV radiator setpoint. When
outdoor air temperature goes below this
setpoint, the ventilation unit starts the
MLV pump. If a message “Preheating
not in use” is displayed, no setpoint is
in use.
3.20
Choosing melting mode
Defrost mode
fan stop
Choose one of the two modes of mel-
ting to be used in the unit. Melting is
done either by stopping the supply air
fan or by bypassing the HR cell. This
setting must not be changed.
3.21
Winter parameter A
Winterparam. A
The winter function of the unit is adju-
sted from the menu when it is not too
cold outside (warmer than –15 °C).
Decreasing the value of the parameter
increases the freezing of the HR cell.
Increasing the value decreases the freezing of the HR cell. The unit ope-
rates optimally on the factory settings. There is no need to adjust this set-
point except in extreme problem situations, and even then it is advisable
to contact Vallox Maintenance. The adjustment is made with the + and
– buttons. See the table for the factory setting.
3.22
Winter parameter B
Winterparam. B
The winter function of the unit is adju-
sted from the menu in very cold weat-
her (colder than –15 °C). Increasing
the value of the parameter increases
the freezing of the HR cell.
Decreasing the value decreases the freezing of the HR cell. The unit
operates optimally on the factory settings. There is no need to adjust this
setpoint except in extreme problem situations, and even then it is advisab-
le to contact Vallox Maintenance. The adjustment is made with the + and
– buttons. See the table for the factory setting.
3.23
Setting base fan speed
MIN speed
1
The desired base fan speed (minimum
fan speed) is chosen with the + and
– buttons. Active when week-clock
control is not on. Week-clock control
changes this speed.