TECHNICAL DATA

2

NOMAK 2x2x0,5+0,5

1

2

1

S

+

A

2x0.5

+

2x0.5

A

+

MAX. 1A, 24VDC

-

B

M

0-10V DC 

S

+

-

B

M

0...10VDC 

2x0.5

2x0.5

A

2x0.5

B

-

+

M S

+

S

+

+

1

2

S

S

GND

%RH1

%RH2

7010101

2011-09-12 pl

0-20mA

R

Mounting, removing and wiring of the control panel

The control panel is wired straight from the electrical connection box. 

The control panel can also be connected in series with a CO

2

 sensor 

or another control panel. (See External electrical connection, page 8.)

Control panel addresses

If two or more control panels are connected to the system, the addresses 

of the control panels need to be changed.

For example 3 control panels

 

• Connect the fi rst control panel to the unit and change its address to 3.
• Connect the second control panel to the unit and change its address 

to 2.
• Connect the third control panel and make sure that its address is 1.
If control panels have the same address, they go to bus fault state. In 

this case, remove one of the control panels and change the address of 

the other panel. The above mentioned situation can arise in connection 

with the later installation of an additional control panel.

External electrical 
connection 
Vallox 121 SE 

(code A3560)

METAL  

= M

WHITE 2 

= B

ORANGE 2 

= A

WHITE 1 

= -

ORANGE 1 

= +

2. TWISTED PAIR
1. TWISTED PAIR

NOTE!

Faulty connection of 

the + wire DESTROYS 

CONTROL PANEL

NOTE!

Faulty connection of the + 

wire DESTROYS THE SENSOR

CONTROL PANEL 1 

ONE OR MORE 

1 INCLUDED AS STANDARD

CO

2

 SENSOR 1 

ONE OR MORE 

OPTION

REMOTE MONITORING

SHORT-CIRCUIT WIRE HAS TO BE 

REMOVED BEFORE CONNECTION

FIREPLACE 

SWITCH

Button switch

(self-resetting contact)

(POTENTIAL-FREE CONTACTS)

THE FIRST HUMIDITY SENSOR 

IS CONNECTED TO REPLACE 

RESISTOR R6k8

HUMIDITY SENSOR %RH2 

OPTION

HUMIDITY SENSOR %RH1 

OPTION

FAULT SIGNAL

FAULT SIGNAL

RS-485 BUS

FIREPLACE SWITCH

FAN CONTROL

PLUG CONNECTION 10 A  

1.2 m ON TOP OF THE UNIT

CONNECTION BOX IS SITUATED 

ON TOP OF THE UNIT

CONNECTION BOX INSIDE 

THE UNIT

Width   90 mm
Height  110 mm
Depth  23 mm

Содержание VALLOX 121 SE L

Страница 1: ...de A3560 Models VALLOX 121 SE R VALLOX 121 SE L Electrical connection 230 V 50 Hz 5 7 A Degree of protection provided by enclosures IP 34 Fans direct current Extract air 0 117 kW 0 9 A 106 dm3 s 100 P...

Страница 2: ...ing to the highest measuring result 1 5 carbon dioxide sensors can be connected as options to the VALLOX 121 SE unit The adjustment is switched on off and if needed the setpoint 500 2000 ppm is set at...

Страница 3: ...ples of such situations are high humidity loads such as a swimming pool or a situation where the exhaust air duct has frozen through Remember Switch post heating off when it starts to get too warm in...

Страница 4: ...u To settings menu see manual In order to move to the Settings menu press the and buttons simultaneous ly In the Settings menu you can chan ge setpoints for the ventilation unit 2 3 Week clock control...

Страница 5: ...tory settings can be restored by pressing the and buttons simultaneously Remember to ensure that the setpoints are in accordance with the factory settings for this unit 3 16 Choosing cascade adjustmen...

Страница 6: ...n speed 2 Sp 2 supply air temperature 17 C Temp 17 Move the cursor to the following hour Monday D 1 16 00 H 16 fan speed 4 Sp 4 supply air temperature 20 C Temp 20 Move the cursor to the following hou...

Страница 7: ...by pulling carefully Place a thin sheet board or paper under the fan in order to prevent the bottom tank from being scratched when removing the fan Unfasten the fixing screw of the fan H hex socket he...

Страница 8: ...es at speed 1 check the fan speed Wiring fault in the carbon dioxide sensor in the control panel or in the humidity sensor or the cable is of the wrong type Contact a maintenance company The connectio...

Страница 9: ...ed operating range Volume flow rate Sound power level in supply air duct one duct by octave band LW dB Sound power level in extract air duct one duct by octave band LW dB ADJUSTMENT POSITION AIR FLOW...

Страница 10: ...R2 Post heating radiator M Damper motor 24 VAC Wire colours s blue m black r brown va white vi green p red h grey kv yellow green 16 V 0 V 0 V 230 V 7023500 2011 11 17 JK M1 GND A B PWM1 PWM2 S RH2 S...

Страница 11: ...ke sure that its address is 1 If control panels have the same address they go to bus fault state In this case remove one of the control panels and change the address of the other panel The above menti...

Страница 12: ...water connections The delivery includes a Silent Kick water seal By connecting a pipe to the water seal the water condensing from extract air can be led to a floor drain not directly to the drain Sil...

Отзывы: