VALLOX DIGIT SE/SE VKL

B

C

A

Heat recovery cell

Pressure difference switch

7

INSTRUCTIONS FOR USE

2.14. Filter guard function

• If DIGIT SE is equipped with a pressure difference switch for the supply and/or extract air

ductwork, the switch monitors the pressure difference in the whole ductwork. When
pressure has risen (e.g. because of a clogged filter), the filter guard symbol ( ) in the main
display of the control panel is lit up.

• The filter guard closes the points of the fault signal relay, and the filter guard symbol ( ) is

seen in the main display.

• The maintenance reminder is on even during this function.
• The operation threshold for the pressure difference switch is adjusted at the pressure

difference switch regulator (0…500 Pa). Factory setting is ca. 260 Pa; the setting can be
changed if needed. With clean filters, the symbol should light up at speeds 7 and 8.

2.15.  Anti-freeze function in water-circulating post-heating unit

• The anti-freeze function aims at preventing a water-circulating post-heating unit from

freezing. The automatic function stops the supply and extract air fans as soon as outdoor
air temperature falls below 0 

°

C and supply air temperature falls below +7 

°

C. At the

same time, the self-actuated dampers of the fans close and the control valve becomes
wide open. The control panel displays the fault message FREEZING ALERT, irrespective of
display.

• The fans start automatically and the dampers open as soon as supply air temperature

exceeds 10 

°

C.

2.16. Fireplace switch / boosting function

Fireplace switch function

• The fireplace switch stops the extract air fan for 15 minutes and causes overpressure in

the ventilation zone. This facilitates lighting up the fireplace, for instance.

• The function is activated by pressing a self-resetting push-button switch. On each pressing

of the switch, the stopping function goes on for 15 minutes.

• During the function, the fireplace/booster switch symbol ( ) is visible in the main display

of the control panel.

Note! When the extract air fan starts, the draft in the fireplace may get weaker!

In cold winter, the anti-freezing and defrosting functions may start when cool air flows to the
extract air ducts. If the post-heating radiator does not contain any non-freezing liquid, there
is a risk of freezing. The situation will get back to normal some time after the function has
stopped.

Booster switch function

• The booster switch raises fan speed to the preset maximum fan speed for 45 minutes.
• The function is activated by pressing a self-resetting push-button switch. On each pressing

of the switch, the stopping function goes on for 45 minutes.

• During the function, the fireplace/booster switch symbol ( ) is visible in the main display

of the control panel.

• The function is selected on the control panel.

© VALLOX • We reserve the right to make changes without prior notification.

2.17. Fault signalling relay (remote monitoring)

• The fault signalling relay has potential free points (24VDC, 1A).
• The points provide information on failure modes of the ventilation unit.
• During water radiator defrosting, the points of the relay close and

open at 10- second intervals.

• High carbon dioxide content alarm switches the relay every second.
• In other failure situations, the points are closed.

2.18. Air filtration

DIGIT SE VALLOX DIGIT SE features coarse filtering of both extract and
supply air before the fans. The unit has a F7 class (B) fine filter and a G3
class (A) coarse filter on the supply side, and a G3 class (C) coarse filter
on the extract side. The filters need to be in place in the unit whenever
ventilation is in operation.

Содержание DIGIT SE

Страница 1: ...ONTROLLER WITH LCD DISPLAY 1 09 61E 27 5 2008 CODE B 3500 SE VALLOX VKL INSTRUCTIONS FOR USE AND MAINTENANCE MODELS VALLOX DIGIT SE VALLOX DIGIT SE VKL VALLOX We reserve the right to make changes with...

Страница 2: ...ing water p 13 5 TROUBLESHOOTING p 16 VALLOX DIGIT SE SE VKL TABLE OF CONTENTS 2 2 VALLOX DIGIT SE models Code B3500 SE VALLOX DIGIT SE Post heating radiator electric radiator 1000 W ALLOX DIGIT SE VK...

Страница 3: ...hroom and the sauna get dry quickly During the heating season the windows and other outer wall structures remain dry Humidity in indoor air is not condensed in the ventilation ducts Air is fresh in th...

Страница 4: ...ventilation 2 2 Ventilation control The unit can be fully controlled with the control panel delivered with the unit or with an optional LON converter The standard week clock control can be used to con...

Страница 5: ...e basic and maximum fan speeds set When the unit is taken into use for the first time with automatic setpoint search selected factory setting it will take the program 3 10 hours to determine the value...

Страница 6: ...ssible To do this the heat recovery bypass function compares the measurement data of the outdoor and extract air sensors The heat recovery cell is bypassed when the post heating function is off when o...

Страница 7: ...ireplace for instance The function is activated by pressing a self resetting push button switch On each pressing of the switch the stopping function goes on for 15 minutes During the function the fire...

Страница 8: ...on 3 1 items 5 and 6 in the figure To settings menu See manual RH1 35 RH2 40 CO2 0821 PPM Out 20 In 20 Sup 20 Exh 20 Temp setting 20C 5 Scrolling up With this button you can scroll the displays upward...

Страница 9: ...ings see manual The adjustment interval for humidity and carbon dioxide adjustments is selected with the and buttons The adjustment interval refers to minutes 3 3 9 Adjustment interval Adjust interval...

Страница 10: ...ired cell bypass temperature is selected with the and buttons If outdoor temperature is lower than cell bypass temperature the summer winter damper is in the winter position 3 3 15 Changing the operat...

Страница 11: ...e word Exit and pressing or Changes in fan speed Sp and supply air temperature Tmp are only made for the hours desired in other cases use N no change to previous Monday D 1 07 00 hours H 7 fan speed 2...

Страница 12: ...nt CO2 900 ppm CO2 Basic humidity level value chosen either automatically or manually Adjustment interval 10 min Freezing protection cell 4 C Freezing protection hysteresis 3 C Preheating setpoint 6 C...

Страница 13: ...of filters The G3 coarse filter A filters insects and coarse pollen and dust The F7 fine filter B filters fine dust that is not discernible to the eye Extract air is filtered with a similar G3 filter...

Страница 14: ...Self actuated one way dampers are only used in VKL model units Observe the position of the damper so that it can also operate on the F7 filter side 4 3 Filter guard DIGIT SE can be equipped with an o...

Страница 15: ...m peratures by 1 or 2 C It extends the period between stop ping and starting See the instructions for using the control panel Section 3 3 22 If the preheating radiator does not operate check if over h...

Страница 16: ...glass tube fuse located in the control card behind a protecting plate the electronics inside the unit may have blown 12 Check the door switch and fuses The unit includes a T800 mA glass tube fuse If...

Отзывы: