The preheating temperature for the anti-frost function in the heat recovery cell is
chosen with the + and – buttons.

3.3.24. Pre-heating temperature for the anti-frost function in the heat recovery cell

Preheater
07C

VALLOX DIGIT SE/SE VKL

INSTRUCTIONS FOR USING THE CONTROL PANEL

10

© VALLOX • We reserve the right to make changes without prior notification.

The hysteresis of the anti-frost function in the heat recovery cell is selected with the + and – buttons.

3.3.22.  Hysteresis of the anti-frost function in the heat recovery cell

Hysteresis
03C

The interval for the maintenance reminder is selected with the + and – buttons. The
maintenance reminder interval refers to months.

3.3.21. Choosing maintenance reminder interval

Maintenance rem.
04

A water or electric radiator is selected with the + and – buttons, depending on the type of post-
heating radiator the unit is equipped with.

Note! Choosing the wrong type of post-heating causes a faulty post-heating function.

3.3.20. Choosing post-heating for the unit

Radiator type
electric rad.

The basic humidity level can be chosen as either automatic or manual. The selection is
done with the + and – buttons.

3.3.19. Choosing the basic humidity level

Rh-level setting
automatic

The desired setpoint is chosen with the + and – buttons when manual adjustment has been selected
as the Rh level setting (humidity setting, section 3.3.19).

3.3.16. Setpoint of the basic humidity level

Basic %RH level
40%

The desired cell bypass temperature is selected with the + and – buttons. If outdoor temperature
is lower than cell bypass temperature, the summer / winter damper is in the winter position.

3.3.15.  Changing the operating temperature of heat recovery cell bypass

Cell bypass
10C

The desired adjustment value for the DC fan is selected with the + and – buttons. The rotation speed
of the supply air fan can be lowered by decreasing the percentage value. If the unit has alternating
current fans, this adjustment has no impact on the functioning of the unit.

3.3.14. Adjusting the direct current fan of the supply air side (does not refer VALLOX DIGIT SE)

DC fan - supply
100%

The mode of operation of the switch (either fireplace or booster switch) is selected
with the + and – buttons.

3.3.17. Mode of operation of the fireplace / booster switch

Switch type
Fireplace switch

Cascade control is activated or deactivated with the + and – buttons.

3.3.18. Choosing cascade control for supply air temperature

Cascade adjust
Off

The setpoint for CO

2

 adjustment is chosen with the + and – buttons.

3.3.25. Changing the setpoint for carbon dioxide adjustment

CO2-setting
0900 PPM

The desired maximum fan speed is selected with the + and – buttons. Maximum fan
speed is on either with adjustments or permanently. See section 3.3.6. Mode of
operation of the maximum speed setting.

3.3.26. Choosing maximum fan speed

MAX speed
8

The stopping temperature of the supply air fan for the anti-frost function in the heat
recovery cell is chosen with the + and – buttons.

3.3.23. Stopping temperature of the supply air fan for the anti-frost function in the heat recovery cell

Supply fan stop
05C

Содержание DIGIT SE

Страница 1: ...ONTROLLER WITH LCD DISPLAY 1 09 61E 27 5 2008 CODE B 3500 SE VALLOX VKL INSTRUCTIONS FOR USE AND MAINTENANCE MODELS VALLOX DIGIT SE VALLOX DIGIT SE VKL VALLOX We reserve the right to make changes with...

Страница 2: ...ing water p 13 5 TROUBLESHOOTING p 16 VALLOX DIGIT SE SE VKL TABLE OF CONTENTS 2 2 VALLOX DIGIT SE models Code B3500 SE VALLOX DIGIT SE Post heating radiator electric radiator 1000 W ALLOX DIGIT SE VK...

Страница 3: ...hroom and the sauna get dry quickly During the heating season the windows and other outer wall structures remain dry Humidity in indoor air is not condensed in the ventilation ducts Air is fresh in th...

Страница 4: ...ventilation 2 2 Ventilation control The unit can be fully controlled with the control panel delivered with the unit or with an optional LON converter The standard week clock control can be used to con...

Страница 5: ...e basic and maximum fan speeds set When the unit is taken into use for the first time with automatic setpoint search selected factory setting it will take the program 3 10 hours to determine the value...

Страница 6: ...ssible To do this the heat recovery bypass function compares the measurement data of the outdoor and extract air sensors The heat recovery cell is bypassed when the post heating function is off when o...

Страница 7: ...ireplace for instance The function is activated by pressing a self resetting push button switch On each pressing of the switch the stopping function goes on for 15 minutes During the function the fire...

Страница 8: ...on 3 1 items 5 and 6 in the figure To settings menu See manual RH1 35 RH2 40 CO2 0821 PPM Out 20 In 20 Sup 20 Exh 20 Temp setting 20C 5 Scrolling up With this button you can scroll the displays upward...

Страница 9: ...ings see manual The adjustment interval for humidity and carbon dioxide adjustments is selected with the and buttons The adjustment interval refers to minutes 3 3 9 Adjustment interval Adjust interval...

Страница 10: ...ired cell bypass temperature is selected with the and buttons If outdoor temperature is lower than cell bypass temperature the summer winter damper is in the winter position 3 3 15 Changing the operat...

Страница 11: ...e word Exit and pressing or Changes in fan speed Sp and supply air temperature Tmp are only made for the hours desired in other cases use N no change to previous Monday D 1 07 00 hours H 7 fan speed 2...

Страница 12: ...nt CO2 900 ppm CO2 Basic humidity level value chosen either automatically or manually Adjustment interval 10 min Freezing protection cell 4 C Freezing protection hysteresis 3 C Preheating setpoint 6 C...

Страница 13: ...of filters The G3 coarse filter A filters insects and coarse pollen and dust The F7 fine filter B filters fine dust that is not discernible to the eye Extract air is filtered with a similar G3 filter...

Страница 14: ...Self actuated one way dampers are only used in VKL model units Observe the position of the damper so that it can also operate on the F7 filter side 4 3 Filter guard DIGIT SE can be equipped with an o...

Страница 15: ...m peratures by 1 or 2 C It extends the period between stop ping and starting See the instructions for using the control panel Section 3 3 22 If the preheating radiator does not operate check if over h...

Страница 16: ...glass tube fuse located in the control card behind a protecting plate the electronics inside the unit may have blown 12 Check the door switch and fuses The unit includes a T800 mA glass tube fuse If...

Отзывы: