VALLOX DIGIT SE/SE VKL

MAINTENANCE INSTRUCTIONS

13

B

A

A

C

T

Preheating

B

A

D

C

F

E

REMEMBER:

Clean the filters at least twice a year. Define the
maintenance reminder interval to suit your
needs; see the instruction in section 3.3.21.
(The interval is dependent on the purity of out-
door and indoor air).

The fine filter (B) cannot be cleaned with water. Clean it in connection with the cleaning
of the G3 filters, vacuuming it with a brush roll. When cleaning, take care not to break
the filtration material. 

To ensure good supply air quality, replace the filter when needed, preferably at

one-year intervals, depending on local air quality

. It is recommended to replace the filters in the

autumn. In this way, the filter will stay fresh during the winter and will efficiently filter dust
in the following spring.
It is advisable to check the cleanliness of the heat recovery cell (C) about every two years,
in connection with the cleaning of the filters. Holding the ears at the end of the cell, pull
the cell out of the unit. If the cell is dirty, wash it by sinking it to water containing washingup
liquid. Rinse the cell clean by showering it with water. When water has flown from between
the sheets, push the cell back into the unit, making sure the sealings against the slide surfaces
are in place and that the "this side up" label at the end of the cell points to the corner
against the upper support.

4. MAINTENANCE INSTRUCTIONS

4.1. Filters

When the maintenance reminder or the filter guard light the indicator
lamp, check the cleanliness of the filters. Outdoor air is filtered in the unit
with two kinds of filters. The G3 coarse filter (A) filters insects and coarse
pollen and dust. The F7 fine filter (B) filters fine dust that is not discernible
to the eye. Extract air is filtered with a similar G3 filter as outdoor air.
Clean the coarse filters (A) when needed i.e by washing them 2 to 4 times
a year and whenever the filter guard indicates a need for maintenance.
When you open thedoor of VALLOX DIGIT SE, the safety switch (T) turns
the unit off. Clean the filters with 25…30

°

C water and washing-up liquid,

pressing them lightly. Do not handle the filters with force. When properly
cleaned, the filters stand cleaning 3 to 4 times. This means 

they have to be

replaced every two years or when needed.

The filters and the heat recovery cell. Units are
either right- or left-handed. In the right-handed
model (R) outdoor air comes to the unit from
the right side of the center line as in these
instructions. In the L model, outdoor air comes
from the left side of the unit. The filters, summer
/ winter damper and heating radiator are also
on opposite sides as compared to the R model.

4.1.1 Preheating filter

If the system has been equipped with optional preheating for preventing
the heat recovery cell from freezing, it needs to be serviced at least twice
a year. The heater (A) has been installed in the outdoor air duct (B).
Remove the plug (C) and inner part (D) of the heater. After this, you can
pull out the filter (E) and its frame (F). Remove the filter from the frame.
You can vacuum the filter or carefully wash it in water under 40

°

C and

a detergent. If the filter is damaged, replace it with a new one. Only use
original filters in the heater. 

USING THE HEATER WITHOUT FILTER IS PROHIBITED

.

Clean the heater of litter and insects at the same time.

© VALLOX • We reserve the right to make changes without prior notification.

Содержание DIGIT SE

Страница 1: ...ONTROLLER WITH LCD DISPLAY 1 09 61E 27 5 2008 CODE B 3500 SE VALLOX VKL INSTRUCTIONS FOR USE AND MAINTENANCE MODELS VALLOX DIGIT SE VALLOX DIGIT SE VKL VALLOX We reserve the right to make changes with...

Страница 2: ...ing water p 13 5 TROUBLESHOOTING p 16 VALLOX DIGIT SE SE VKL TABLE OF CONTENTS 2 2 VALLOX DIGIT SE models Code B3500 SE VALLOX DIGIT SE Post heating radiator electric radiator 1000 W ALLOX DIGIT SE VK...

Страница 3: ...hroom and the sauna get dry quickly During the heating season the windows and other outer wall structures remain dry Humidity in indoor air is not condensed in the ventilation ducts Air is fresh in th...

Страница 4: ...ventilation 2 2 Ventilation control The unit can be fully controlled with the control panel delivered with the unit or with an optional LON converter The standard week clock control can be used to con...

Страница 5: ...e basic and maximum fan speeds set When the unit is taken into use for the first time with automatic setpoint search selected factory setting it will take the program 3 10 hours to determine the value...

Страница 6: ...ssible To do this the heat recovery bypass function compares the measurement data of the outdoor and extract air sensors The heat recovery cell is bypassed when the post heating function is off when o...

Страница 7: ...ireplace for instance The function is activated by pressing a self resetting push button switch On each pressing of the switch the stopping function goes on for 15 minutes During the function the fire...

Страница 8: ...on 3 1 items 5 and 6 in the figure To settings menu See manual RH1 35 RH2 40 CO2 0821 PPM Out 20 In 20 Sup 20 Exh 20 Temp setting 20C 5 Scrolling up With this button you can scroll the displays upward...

Страница 9: ...ings see manual The adjustment interval for humidity and carbon dioxide adjustments is selected with the and buttons The adjustment interval refers to minutes 3 3 9 Adjustment interval Adjust interval...

Страница 10: ...ired cell bypass temperature is selected with the and buttons If outdoor temperature is lower than cell bypass temperature the summer winter damper is in the winter position 3 3 15 Changing the operat...

Страница 11: ...e word Exit and pressing or Changes in fan speed Sp and supply air temperature Tmp are only made for the hours desired in other cases use N no change to previous Monday D 1 07 00 hours H 7 fan speed 2...

Страница 12: ...nt CO2 900 ppm CO2 Basic humidity level value chosen either automatically or manually Adjustment interval 10 min Freezing protection cell 4 C Freezing protection hysteresis 3 C Preheating setpoint 6 C...

Страница 13: ...of filters The G3 coarse filter A filters insects and coarse pollen and dust The F7 fine filter B filters fine dust that is not discernible to the eye Extract air is filtered with a similar G3 filter...

Страница 14: ...Self actuated one way dampers are only used in VKL model units Observe the position of the damper so that it can also operate on the F7 filter side 4 3 Filter guard DIGIT SE can be equipped with an o...

Страница 15: ...m peratures by 1 or 2 C It extends the period between stop ping and starting See the instructions for using the control panel Section 3 3 22 If the preheating radiator does not operate check if over h...

Страница 16: ...glass tube fuse located in the control card behind a protecting plate the electronics inside the unit may have blown 12 Check the door switch and fuses The unit includes a T800 mA glass tube fuse If...

Отзывы: