background image

4.2. Fans and post-heating radiator

The supply and extract air fans (D and E) have been fastened with rubber
collars (F). When removing the fans for maintenance, remove the one-way
dampers (L) from the VKL model, open the ear (K) attached to the fan, bent
over the rubber collar. Then lift the rubber collar away and turn the fan away
from above the lower support (M) made of rubber. Then take the electrical
connector (G) off from behind the fan.
Clean the fan blades with compressed air.

If you use water when cleaning the unit or its parts, do not let water enter the electric parts.

For cleaning the post-heating radiator (J), remove the filters and the heat
recovery cell. Clean the post-heating radiator while it is in place in the unit
either by vacuuming it or blowing it with compressed air. The radiator can be
either electric or water circulated. If needed, you can remove the electric
radiator for maintenance by removing the electrical connector (H) as well as
the two tightening-up screws (I) and the adhesive or screw fixing the support
against the bottom reservoir.

4.2.1.

Detaching and attaching of one-way damper.

Detaching and attaching of self-actuated one-way damper (vacuum damper):
A Put the hook on the rim of the damper (Y) under the side edge of the

fastening collar (K) of the fan (F). Then push the damper downwards so
that the guide edges of the valve go inside the rubber collar.

B Push the other side of the collar with a finger.
C Put the hook on the other side edge of the damper below the edge of the

collar.

To detach the damper take the same steps in the opposite order.

Self-actuated one-way dampers are only used in VKL model units. Observe
the position of the damper so that it can also operate on the F7 filter side.

4.3. Filter guard

DIGIT SE can be equipped with an optional filter guard. The filter guard symbol ( ) normally
lights up in the main display at speeds 7 and 8, when the filters are clean, and this does
not cause any service activities. If the symbol does not light up at speed 8, the pressure in
the ventilation ductwork of the building differs from the factory setting. In that case, adjust
the filter guard setpoint lower in the inside of the unit (see Section 2.14). If the filter guard
symbol lights up at fan speed 4 or 5, the filters need cleaning. If they are clean, the lighting
up may be caused by too dense a mosquito net installed in the external grille or by the
closing of the supply air valves in the rooms. If, after checking these things, the symbol
continues to light up at small speeds, adjust the setpoint greater.

4.4. Condensing 

water

During the heating season, the humidity in extract air condenses as condensing water. Water
formation may be abundant in new buildings or if ventilation is scarce in terms of moisture
production by the inhabitants. The condensing water must exit the unit without hindrance.
In connection with maintenance operations, for example in the autumn before the start of
the heating season, make sure that the condensing water joint (L) in the bottom reservoir is
not clogged. You can check this by pouring a little water in the reservoir. Clean if needed.
Do not let any water enter the electrical devices.

VALLOX DIGIT SE/SE VKL

14

MAINTENANCE INSTRUCTIONS

© VALLOX • We reserve the right to make changes without prior notification.

F

K

Y

F

K

Y

F

K

Y

F

K

Y

A

B

C

F

P

L

E

G

D

G

H

I

J

M

M

L

F

K

K

Q

Содержание DIGIT SE

Страница 1: ...ONTROLLER WITH LCD DISPLAY 1 09 61E 27 5 2008 CODE B 3500 SE VALLOX VKL INSTRUCTIONS FOR USE AND MAINTENANCE MODELS VALLOX DIGIT SE VALLOX DIGIT SE VKL VALLOX We reserve the right to make changes with...

Страница 2: ...ing water p 13 5 TROUBLESHOOTING p 16 VALLOX DIGIT SE SE VKL TABLE OF CONTENTS 2 2 VALLOX DIGIT SE models Code B3500 SE VALLOX DIGIT SE Post heating radiator electric radiator 1000 W ALLOX DIGIT SE VK...

Страница 3: ...hroom and the sauna get dry quickly During the heating season the windows and other outer wall structures remain dry Humidity in indoor air is not condensed in the ventilation ducts Air is fresh in th...

Страница 4: ...ventilation 2 2 Ventilation control The unit can be fully controlled with the control panel delivered with the unit or with an optional LON converter The standard week clock control can be used to con...

Страница 5: ...e basic and maximum fan speeds set When the unit is taken into use for the first time with automatic setpoint search selected factory setting it will take the program 3 10 hours to determine the value...

Страница 6: ...ssible To do this the heat recovery bypass function compares the measurement data of the outdoor and extract air sensors The heat recovery cell is bypassed when the post heating function is off when o...

Страница 7: ...ireplace for instance The function is activated by pressing a self resetting push button switch On each pressing of the switch the stopping function goes on for 15 minutes During the function the fire...

Страница 8: ...on 3 1 items 5 and 6 in the figure To settings menu See manual RH1 35 RH2 40 CO2 0821 PPM Out 20 In 20 Sup 20 Exh 20 Temp setting 20C 5 Scrolling up With this button you can scroll the displays upward...

Страница 9: ...ings see manual The adjustment interval for humidity and carbon dioxide adjustments is selected with the and buttons The adjustment interval refers to minutes 3 3 9 Adjustment interval Adjust interval...

Страница 10: ...ired cell bypass temperature is selected with the and buttons If outdoor temperature is lower than cell bypass temperature the summer winter damper is in the winter position 3 3 15 Changing the operat...

Страница 11: ...e word Exit and pressing or Changes in fan speed Sp and supply air temperature Tmp are only made for the hours desired in other cases use N no change to previous Monday D 1 07 00 hours H 7 fan speed 2...

Страница 12: ...nt CO2 900 ppm CO2 Basic humidity level value chosen either automatically or manually Adjustment interval 10 min Freezing protection cell 4 C Freezing protection hysteresis 3 C Preheating setpoint 6 C...

Страница 13: ...of filters The G3 coarse filter A filters insects and coarse pollen and dust The F7 fine filter B filters fine dust that is not discernible to the eye Extract air is filtered with a similar G3 filter...

Страница 14: ...Self actuated one way dampers are only used in VKL model units Observe the position of the damper so that it can also operate on the F7 filter side 4 3 Filter guard DIGIT SE can be equipped with an o...

Страница 15: ...m peratures by 1 or 2 C It extends the period between stop ping and starting See the instructions for using the control panel Section 3 3 22 If the preheating radiator does not operate check if over h...

Страница 16: ...glass tube fuse located in the control card behind a protecting plate the electronics inside the unit may have blown 12 Check the door switch and fuses The unit includes a T800 mA glass tube fuse If...

Отзывы: