background image

18

TECHNIC

AL SPECIFIC

ATIONS

Always follow first and foremost the connection diagram 

provided by the HVAC designer or heat pump manufacturer. 

Also read the duct radiator manual. 
The accompanying figure shows an example of the 

arrangement for connecting the heating/cooling radiator unit 

to the heat collection circuit.
Connect the radiator output pipe to the heat collection circuit 

return pipe. Direct the fluid returning from the radiator unit to 

the heat collection circuit return pipe. If you know that there 

is a large loss of internal pressure inside the heat pump, the 

heat pump should be bypassed. If this is done, the fluid circuit 

will come into operation when the heat pump comes to a halt. 

When this happens the pressure loss in the one-way bypass 

valve Y2 must be lower than the pressure loss in the heat 

pump.

Heating:

 The pump starts when the outdoor air temperature 

drops below the winter limit value set at the factory (-5 °C).

Cooling 

The supply air setpoint value for the active mode 

(for example, At home) controls the pump start-up. The pump 

starts when the supply air setting is below the temperature of 

the supply air that is blown into the apartment.
The duct radiator can be installed in both the supply air 

duct and the outdoor air duct. If the radiator is installed in 

the outdoor air duct, it can be used for both preheating and 

cooling, or for preheating or cooling alone. If the radiator 

is installed in the supply air duct, it can be used only for 

preheating or cooling.

The duct radiator can be set to function either automatically 

or manually. 

•  Automatic

 - In summer, the supply air temperature will 

be maintained at the level specified in the temperature 

setting. In winter, the duct radiator will turn on, when the 

outdoor temperature falls below the winter setting.

•  Manual

 - In summer, the duct radiator will turn on, when 

the outdoor temperature rises above the summer setting. 

In winter, the duct radiator will turn on, when the outdoor 

temperature falls below the winter setting.

To prevent the risk of condensation in the supply air duct, you 

can set the adjustment of the supply air limit to automatic or 

manual. 

•  Automatic

 - The supply air limit is adjusted automatically 

based on the dew point of the extract air. When the supply 

air temperature falls too low, the duct radiator will turn off.  

•  Manual

 - The supply air limit can be set manually. When 

the supply air temperature falls down to the set value, the 

duct radiator will turn off.

If an external sensor is in use, it is selected from the settings 

of the external sensor whether it is used to control the outdoor 

air duct radiator or the supply air duct radiator.

NOTE:

 If the duct 

radiator is used in 

the supply air duct, it 

can only be used for 

cooling. 

NOTE:

 When used to 

control the outdoor air 

duct radiator, the exter-

nal NTC sensor is ins-

talled in the outdoor air 

duct before the radiator. 

When used to control 

the supply air duct ra-

diator, the external NTC 

sensor is installed after 

the radiator.

NOTE:

When selecting the 

relay (C), take account 

of the maximum 

allowed combined 

power supply (6W) of 

the circuit board in the 

external MV electrical 

box, if the relay power 

supply comes from the 

circuit board’s +24V 

connector.

NOTE:

Due to the risk of humi-

dity damage, in a duct 

that has not been insu-

lated for condensation 

the supply air tempera-

ture must not fall below 

+16 … 20 °C.

DUCT RADIATOR OPERATION

Содержание A3741

Страница 1: ...Manual Model Vallox 101 MV Type A3741 Document D5331 Valid from 24 02 2020 Updated 05 02 2020 Ventilation unit MANUAL...

Страница 2: ...required by the alternative Vallox Silent Klick siphon installation method elbow 9 Measuring and adjusting the air flows of the ventilation unit 9 Dimensions and duct outlets 10 MAINTENANCE 11 Before...

Страница 3: ...al installations and connections must be carried out only by an electrician and in compliance with local regulations GUARANTEE The guarantee and liability exclude damage resulting from Inappropriate u...

Страница 4: ...result in death or serious injury if not avoided IMPORTANT Indicates a hazard that can result in damage to property or loss of data if not avoided CAUTION Indicates a hazard that can result in minor...

Страница 5: ...ws for controlling ventilation remotely also using e g a smartphone or tablet Also the unit software is updated automatically through the cloud service To connect to the cloud service the ventilation...

Страница 6: ...l in the figure MAIN PARTS Post heatingresistor in the supply air duct 8 Safety switch 9 Internal humidity sensor 10 Control panel 11 Carbon dioxide sensor optional 12 Humidity sensor optional 13 VOC...

Страница 7: ...is determines the position of the unit The top edge of the white covering strip of the ceiling mounting plate can be installed against the ceiling Alternatively a concealed mounting method can be used...

Страница 8: ...x can be accessed The distance between the service door and the ceiling mounting plate must be around 500 mm Alternatively the cables can be fed between the ceiling mounting plate and the ventilation...

Страница 9: ...ing tubes These can be inserted in the ducts to allow for easier ventilation adjustment NOTE The Vallox Silent Klick siphon package is delivered with the unit Installation instructions for the siphon...

Страница 10: ...ating resistor in the supply air duct 9 Safety switch 10 Internal humidity and carbon dioxide sensor Dimensions and duct outlets Dimensions Duct outlets R model Inner diameter of the female collar 125...

Страница 11: ...very cell clean The filter replacement interval depends on the ambient particle concentration It is recommended that the filters be replaced every spring and autumn or at the very least once a year To...

Страница 12: ...rip E in place so that the strip is supported by the corner bracket G at the rear 13 Install the extract air filter C in place 14 Close the door Ensure that the safety switch catch of the door is touc...

Страница 13: ...the rubber feed through I into the fan chamber 7 Remove the wing screws used to fasten the fans J 3 screws per fan 8 Remove the fan from the unit by pulling it forward and by tilting it slightly backw...

Страница 14: ...evel in the supply air duct one duct by octave band Lw dB Sound power level in the extract air duct one duct by octave band Lw dB Adjustment position Adjustment position Adjustment position 4 14 22 33...

Страница 15: ...ignal RS_B Local hardware Modbus B signal NTC External temperature sensor connector D I1 Digital input 1 D I2 Digital input 2 11V1 11 1 V operating voltage AN I Analog input 0 10VDC RM I 24V relay inp...

Страница 16: ...ut EXTERNAL ELECTRICAL CONNECTION 3x1 5S 2x2x0 5 0 5 2x0 5 2x0 5 7028350 2014 08 29 JS 2x2x0 5 0 5 2x0 5 2x2x0 5 0 5 2x2x0 5 0 5 2x2x0 5 0 5 2x0 5 2x0 5 CAT Analog input two different functions Potent...

Страница 17: ...rd MLV control External temperature sensor NTC 4K7 MB_A External Modbus A signal MB_B External Modbus B signal 24V 24V voltage DC GND Digital and analog ground potential RS_A Local hardware Modbus A s...

Страница 18: ...the supply air temperature will be maintained at the level specified in the temperature setting In winter the duct radiator will turn on when the outdoor temperature falls below the winter setting Ma...

Страница 19: ...ve Not included in the delivery The valve that is chosen must be compatible with the heat collection circuit fluid for example ELV05006 Stig Wahlstr m K Condensing water tube Not included in the deliv...

Страница 20: ...lent Klick 3494701 14 Door 4102334 24 MyVallox humidity sensor optional 946149 5 Coarse and fine filter for supply air 978225 15 Mounting screw of the door 990712 25 MyVallox carbon dioxide sensor opt...

Страница 21: ...CONFORMITY CERTIFICATES...

Страница 22: ...22...

Страница 23: ...23 Vallox Oy All rights reserved...

Страница 24: ...D5331 04 02 2020FIN 05 02 2020ENG PDF www vallox com Vallox Oy Myllykyl ntie 9 11 32200 LOIMAA FINLAND Customer service 358 10 7732 200 Aftersales 358 10 7732 270...

Отзывы: