- 5 -
Product Model
V1-08
V1-13
Heating
Heating Capacity Range
(kW)
1.57~8.40
4.40~13.00
Heating Input Range (kW)
0.32~1.87
0.90~3.02
Current Range (A)
1.42~8.30
1.39~4.68
COP Range
4.49~4.91
4.30~4.90
Cooling
Cooling Capacity Range (kW)
0.99~6.22
2.80~8.20
Cooling Input Power (kW)
0.29~2.18
0.85~3.31
Current Range (A)
1.28~9.67
1.32~5.13
EER Range
2.85~3.41
2.48~3.29
DHW
Heating Capacity Range
(kW)
1.28~6.81
3.52~10.50
Heating Input Range (kW)
0.31~2.13
0.88~3.39
Current Range (A)
1.38~9.45
1.36~5.26
COP Range
3.2~4.1
3.1~4.0
Power Supply
230V/1Ph/50-60Hz
380V/3Ph/50-60Hz
Working Ambient Temperature
-30~43
℃
Refrigerant
R32/1.3kg
R32/1.6kg
Compressor Brand
Panasonic
IP Grade (Level of Protection)
IPX4
IPX4
Anti-electric Shock Rate
I
I
Noise (dB(A))
≤53
≤55
Water Pressure Drop (kPa)
31
25
Water Circulation (m³/H)
1.4
2.2
Diameter of Pipe (mm)
DN25
DN25
Body Size (W*D*H) (mm)
970×475×835
1100×475×985
Packing size(W*D*H)(Polywood)
1048×520×974
1140×515×1110
Packing Size (W*D*H) (Carton)
1028×520×974
1120×515×1108
Net Weight / Gross Weight (kg)
110/120
140/150
Remark:
Heating working condition: Inlet water temperature 30
℃
, Outlet water temperature 35
℃
, Dry bulb temperature 7
℃
, Wet
bulb temperature 6
℃
.
Cooling working condition: Inlet water temperature 12
℃
, Outlet water temperature 7
℃
, Dry bulb temperature 35
℃
, Wet
bulb temperature 24
℃
.
DHW working condition: Inlet water temperature 15
℃
, Outlet water temperature 55
℃
, Dry bulb temperature 7
℃
, Wet bulb
temperature 6
℃
.
Содержание V1 Series
Страница 9: ...8 V1 18 V1 23 V1 28 V1 35...
Страница 10: ...9 Exploded view V1 08...
Страница 11: ...10 V1 13...
Страница 12: ...11 V1 18 23...
Страница 13: ...12 V1 28 35...
Страница 16: ...15 Figure 2 Figure 3...
Страница 18: ...17 Figure 7 Figure 8...
Страница 20: ...19 Figure 11 Figure 12 Figure 13...
Страница 23: ...22 Electrical Wiring Diagram 1 Single phase system V1 08...
Страница 24: ...23 2 Three phase system V1 13 18 23...
Страница 25: ...24 3 Three phase system V1 28 35...