- 34 -
forced to turn on.
◎
During the Antisepsis process, if the water tank temperature > 60
℃
(the maximum settable
temperature), then the compressor will not start, but only start electric heating; if the water
tank temperature
≤55
℃
, both the compressor and electric heater will start.
◎
When the water tank
temperature ≥65
℃
(P20) and the protection temperature lasts for 15
minutes (P19)
≥65
℃
, exit the high temperature Antisepsis.
◎
After entering high temperature Antisepsis, if the temperature of the hot water tank does
not reach 65°C after 1 hour, the high temperature Antisepsis program will be forced to exit.
Target Temperature Auto Adjustment Logic (Under Heating Mode)
◎
The target temperature under heating mode can be automatically adjusted according to
the ambient temperature.
◎
Entry conditions
When Parameter P22=1 enables automatic adjustment mode of heating target temperature.
◎
Calculation formula of heating target temperature
Pset (heating target temperature) = 20 + (P24/10) * (P23 - current ambient temperature)
◎
The above different curves stands for the different value of P24.
(When P24=1, the actual value is 0.1)
◎
The target temperature range of automatic temperature adjustment is 20-60
℃
Auxiliary Electric Heater for Water Tank
◎
Start conditions (all below conditions must be met at the same time)
Содержание V1 Series
Страница 9: ...8 V1 18 V1 23 V1 28 V1 35...
Страница 10: ...9 Exploded view V1 08...
Страница 11: ...10 V1 13...
Страница 12: ...11 V1 18 23...
Страница 13: ...12 V1 28 35...
Страница 16: ...15 Figure 2 Figure 3...
Страница 18: ...17 Figure 7 Figure 8...
Страница 20: ...19 Figure 11 Figure 12 Figure 13...
Страница 23: ...22 Electrical Wiring Diagram 1 Single phase system V1 08...
Страница 24: ...23 2 Three phase system V1 13 18 23...
Страница 25: ...24 3 Three phase system V1 28 35...
Страница 38: ...37 use G If the unit is soaking please contact the supplier factory or company of installment before use...