5.4.3
Pump Control menu
Pump Control
Default
Values
Reset
Description
1 Pump
1 Output
None
A
Configure pump output signal
2 Controller
The status of the pump controller
1 Always off
√
A
The pump is always off
2 Always on
The pump is always on
3 Auto
The pump controller is active
4 Manual
Manual control the pump
3 Motor safety relay
None
A
Select the input signal
4 Max running time
Configure the max running time
1 Status
Off
On/off
Status of the maximum running time function
2 Time
120
0-255 sec
A
Set the time the pump is active before a warning appears
2 Pressure
1 Loop
Configuration if using a pressure transmitter
1 Pump configuration
Configure the levels which starts and stops the pump
1 Pump start
80 bar
0 - 500 bar
A
Start pump when pressure is below this value
2 Pump stop
120 bar
0 - 500 bar
A
Stop the pump when the pressure is above this value
3 Level
1 Loop
Configuration if using a level transmitter
1 Pump stop
100 mm
0-9999 mm
A
Stop the pump when the level is below this value
2 Loop configuration
Configure the connected level transmitter
1 Loop 4mA value
0 mm
0-9999 mm
A
Level at 4mA
2 Loop 20mA value
700 mm
0-9999 mm
A
Level at 20mA
4 Temperature
1 Loop
Configuration if using a temperature transmitter
1 Pump stop high
Pump stop high cofiguration
1 Status
Off
On/off
Turn the pump stop high function on and off
2 Pump stop
80
°
C
-200 - 850 °C
A
Stop the pump when the temperature is above this value
2 Pump stop low
Pump stop low cofiguration
1 Status
Off
On/off
Turn the pump stop low function on and off
2 Pump stop
-20
°
C
-200 - 850 °C
A
Stop the pump when the temperature is below this value
5 Valve
1 Pump start
1 Valve open
√
Start pump when valve opens
2 Valve close
√
Start pump when valve closes
3 Valve stayput
√
Start pump when valve goes to stayput
2 Pump stop
1 Delay
5 sec
0-240 sec
Keeps the pump running after start command has ended
More settings are available through ValConnect.