5.4.2
Advanced menu
Advanced menu
Default
Reset Description
1 Manual Control
Manual control of positioner.
1 Setpoint
Manual control of set point
2 Actuator
Manual control of control valves
3 Actuator pulse
Manual control of control valves using pulses only
4 Control valves
Manual control of individual control valves
2 Signal Calibration
Calibration of signals to control room
1 Control loop
Calibration of 4-20 mA control signal
2 Transmitter loop
Calibration of 4-20 mA transmitter signal
3 Position loop
Calibration of 4-20 mA position loop
4 AI2
Calibration of 4-20 mA analogue input 1
5 AI3
Calibration of 4-20 mA analogue input 2
6 AI4
Calibration of 4-20 mA analogue input 3
7 AI5
Calibration of 4-20 mA analogue input 4
8 AO1
Calibration of 4-20 mA analogue output 1
9 AO2
Calibration of 4-20 mA analogue output 2
3 Configuration
Configuration of in- and outputs
1 Valve function
Configuration of valve control
1 Open
Not used
A
Menu to select valve position to open actuator
2 Close
Not used
A
Menu to select valve position to close actuator
3 Stay-put
Not used
A
Menu to select valve position to keep current actuator position
4 Fail position
Off
A
Menu to select valve position at fail position
2 Position feedback
Position feedback input
1 Position sensor
A
Potentiometer input
2 Position loop
√
4-20mA input
3 End position
Configuration of endposition signal
1 Output signal 0%
Not used
A
Select output which is active at 0%
2 Output signal 100%
Not used
A
Select output which is active at 100%
3 Deadband
0.5%
A
Deadband for endpoint signal
4 Off/Local
A
Configure off/local signal
1 Off signal
Not used
A
Select off signal input
2 Local signal
Not used
A
Select local signal input
5 Man. valve control
Configure the manaul control when in local mode
1
Open signal
Not used
A
Select input to open valve
2
Close signal
Not used
A
Select input to close valve
6 Emergency shutdown
Configure Emergency shutdown
1 Input signal
Not used
A
Select input to ESD signal
7 Error signal
Configure error signal
1 Output signal
Not used
A
Select output port for error signal
8 Ok signal
Configure ok signal
1 Output signal
Not used
A
Select output port for ok signal
9 Linear correction
Calibrate the linearity of the position feedback
1 Status
Enable the linear correction
2 Calibrate
Perform the linear calibration