Error no.
7.1
Mounting and settings
No. 101
Solenoids are not configured
Description
The Valve Function has not been configured in the menu
Trouble shooting
Configure the Valve Function in the advanced menu (3.1)
Consequence
The positioner outputs goes to their fail position.
No. 102
Potentiometer is not connected
Description
The potentiometer has been selected as the position feedback signal, but there
is not connected a potentiometer to the positioner.
Trouble shooting
Connect a potentiometer to the positioner
Or
Change the position feedback signal to position loop in the advanced menu
(3.2)
Consequence
The positioner outputs goes to their fail position.
No. 103
Position loop is not connected
Description
The position loop has been selected as the position feedback signal, but there
is not connected a signal to the positioner.
Trouble shooting
Connect a loop signal to the positioner
Or
Change the position feedback signal to potentiometer in the advanced menu
(3.2)
Consequence
The positioner outputs goes to their fail position.
No. 104
Control loop is not connected
Description
A control loop has not been connected to the positioner
Trouble shooting
Connect a control loop to the positioner
Consequence
The positioner outputs goes to their fail position.