DHP-UM-020
Val Controls A/S
•
Limfjordsvej 3
•
DK-6715 Esbjerg N
•
Tel. +45 7547 0600
•
Fax +45 7547 0611
•
www.valcontrols.com
Revision: 12
15/38
5.4.1
Basic menu
Basic menu structure.
Basic
Default
Reset
Description
1 Deadband
1.0
B A
Acceptable deviation from setpoint in percentage
2 Flow curve
Choice of flow curve
1 Linear
√
B A
Linear flow curve
2 Equal pct. 50:1
Equal percentage 50:1 flow curve
3 Custom
Custom flow curve
3 Valve action
Valve action
1 Direct
√
B A
Valve opens with increasing setpoint value
2 Reverse
Valve closes with increasing setpoint value
4 Regulator functions
Special function on how the positioner works
1 End settings
Settings when the setpoint signal is 0% or 100%
1 Hold at open
Function at 100%
1 Status
Off
B A
Timer starts at 100%
2 Time
5
B A
Time before positioner goes to stay-put
2 Hold at close
Function at 0%
1 Status
Off
B A
Timer starts at 0%
2 Time
5
B A
Time before positioner goes to stay-put
5 Transmitter
Transmitter settings
1 Transmitter action
Transmitter action
1 Direct
√
B A
0% flow = 4mA
2 Reverse
0% flow = 20mA
2 Transmitter fail position
Transmitter fail
1 None
√
B A
During a failure will the transmitter show the position
2 3.5 mA
During failure the transmitter will be 3.5mA
3 21.5 mA
During failure the transmitter will be 21.5mA
6 Display
Display settings
1 Display light
Off
B A
Controlling the diplay light
2 Contrast
5
B A
Controlling the diplay contrast
3. Frontpage
Configure the frontpage
1 Valve position
B A
Selcet who to display the position of the valve
1 Percent
√
Show valve position in percent
2 Degree
Show valve position in degree
2 Configuration
Configuration for for the frontpage
1 Action
Direct
B A
Set the direction of the valve position on the frontpage
2 Degree min
0
°
B A
Degree at 0%
3 Degree max
90°
B A
Degree at 100%
7 Status indicators
Status indicators
1 Status
On/Off
Enable status indicators
8 MT control
Magnetic touch control
1 Status
On/Off
Enable MT control
2 Auto lock status
On/Off
Enable auto lock for MT control
3 Auto lock time
1 min
Set the auto lock time