Stay-put position: Tune the 12mA output when only one AO is used. Used for proportional
valves that has a spool which is out of the centre.
•
Propor. fail pos: Set the fail position of the analogue output.
o
4mA
o
12mA (Default)
o
20mA
Control parameters
•
Hysteresis: The hysteresis at the setpoint
•
Pos. ADC 1
st
end: Fine adjust the 1
st
end point
•
Pos. ADC 2
nd
end: Fine adjust the 2
nd
end point
The following parameters can only be accessed through ValConnect.
•
Slow speed open: Set the minimum speed when opening
•
Slow speed close: Set the minimum speed when opening
•
Speed open: Set the normal speed when opening
•
Speed close: Set the normal speed when closing
•
Acceleration open: Set the acceleration time when opening
•
Acceleration close: Set the acceleration time when closing
•
Deceleration open: Set the deceleration time when opening
•
Deceleration close: Set the deceleration time when closing
•
Slow open dist: Set the distance before the set point that deceleration will start when
opening
•
Slow close dist: Set the distance before the set point that deceleration will start when closing